Mdu Settings - Huawei UPS5000 User Manual

Backfeed protection card
Hide thumbs Also See for UPS5000:
Table of Contents

Advertisement

UPS5000 Backfeed Protection Card
User Manual (03021KQQ)
If MUE06A connection is set to Enable and communication between the backfeed protection
card and the UPS fails, a Dry contact board fault alarm will be triggered. The following
describes how to enable the alarm. You can set the parameters either on the LCD or web user
interface (WebUI).
LCD
Step 1 Choose System Info > Settings > Dry Contacts.
Step 2 On the Dry Contacts screen, set MUE06A connection to Enable, as shown in
Figure 4-1 Setting parameters on the LCD
----End
Issue 05 (2017-04-28)
If you have not logged in, enter a user name and password (the preset passwords for admin and operator
on the LCD are both 000001), and tap
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4

MDU Settings

on the login screen displayed.
4 MDU Settings
Figure
4-1.