Replacement Of The Pressure Sensor (Psw); Replacement Of The Pressure Relief Valve; Replacement Of The Sight Glass; Replacement Of The Stop Valve (X3) - Hitachi SAMURAI Series Service Manual

Water cooled water chillers -modular-r134a-screw type
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

3 Servicing
Cycle components

3.3.13 Replacement of the pressure sensor (PSW)

1 Disconnect the cables (7 and 8 of the pressure
sensor form the E-box of the compressor
terminal board).
2 Unscrew the sensor and proceed to its
replacement
3 When reassembling proceed in reverse order
than removing.

3.3.14 Replacement of the pressure relief valve

1 Remove the relief valve unscrewing the valve
with a spanner.
2 When reassembling after replacing the relief
valve, proceed in the reverse order than
removing. Use Teflon tape on the thread to
avoid any leakage.

3.3.15 Replacement of the sight glass

To remove the sight glass proceed as follows:
1 Remove the brazed parts using a blowtorch
and previously cooling the pipe side and the
sight glass with wet cloth in order to avoid
brazing material enter inside the pipes.
2 When reassembling after replacing the sight
glass, perform the procedure in the reverse
order than removing.

3.3.16 Replacement of the stop valve (x3)

There are 3 stop valves located along the refrigerant cycle: 2 are located close the expansion valves and 1 is located at
the filter drier, as shown in the pictures below.
At expansion valves
To replace the stop valves, unscrew the stop valve with a spanner. Remove and replace the stop valve. Use Teflon tape
to seal the thread and avoid any leakage.
74
SMGB0120 rev.0 - 11/2017
Pressure sensor
(PSW)
Relief valve
Sight glass
Stop valve (x3)
At filter drier
Brazed parts

Advertisement

Table of Contents
loading

Table of Contents