Error Display - LG PRCKD20E Owner's Manual

Ahu control kit
Hide thumbs Also See for PRCKD20E:
Table of Contents

Advertisement

Test run
Error display (AHU)
I '##' refers to the address information of the communication PCB.
Display
Error item
number
CH 2 ##
Temperature sensor
error at pipe inlet of
indoor unit
CH 3 00
Communication error
between wired remote
controller and AHU
controller
CH 4 ##
Communication error
between AHU
controller and
communication PCB
CH 5 ##
Communication error
between
communication PCB
and outdoor unit
CH 6 ##
Temperature sensor
error on pipe outlet of
indoor unit
CH 8 00
Emergency operation
CH 13 01
Temperature sensor
error
02
04
CH 14 01
Humidity sensor error
02
03
CH 15 00
CO
sensor error
2
CH 16 05
Pressure sensor error
06
CH 17 01
Air flow sensor error
02
32 AHU CONTROL KIT
Cause of error
Communication PCB
Temperature sensor disconnection or short circuit at pipe inlet
rotary switch number
of indoor unit
##
No communication signal for more than 3 minutes from wired
-
remote controller to the AHU controller
Communication PCB
No communication signal for more than 3 minutes from
rotary switch number
communication PCB to AHU controller
##
Communication PCB
No communication signal for 5 minutes continuously from
rotary switch number
communication PCB to outdoor unit
##
Communication PCB
Temperature sensor disconnection or short circuit on pipe
rotary switch number
outlet of indoor unit
##
-
The operating status of the smoke control mode through smoke detector is displayed
RA
Temperature sensor (RA/SA/Mixing) disconnection/short
circuit/misconnection or when the sensor value is in the error
SA
range
Mixing
RA
Humidity sensor (RA/SA/OA) disconnection/short
SA
circuit/misconnection or when the sensor value is in the error
OA
range
-
CO
the sensor value is in the error range
Differential pressure
Pressure sensor (Differential pressure, static pressure) disconnection/short
Static pressure
circuit/misconnection or when the sensor value is in the error range
RA
Air flow sensor (RA, SA) disconnection/short circuit/misconnection
SA
or when the sensor value is in the error range
Cause or error
sensor disconnection/short circuit/misconnection or when
2