17.5.16 Outdoor High Pressure Switch Activate (F12)
Malfunction Decision Conditions:
During operation of heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch.
Malfunction Caused:
1
Faulty water pump.
2
Insufficient water flow rate in system.
3
Water leak in system.
4
3 way valve closed.
5
Clogged expansion valve or strainer.
6
Excessive refrigerant.
7
Faulty outdoor high pressure sensor and switch.
8
Faulty outdoor unit PCB.
Abnormality Judgment:
Continue 4 times in 20 minutes.