11.3.4 CONNECT THE CABLE TO THE INDOOR UNIT
1
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 4.0
2
or 6.0 mm
flexible cord, type designation 60245 IEC 57 or heavier cord.
Ensure the colour of wires of outdoor unit and the terminal no. are the same to the indoor unit's
o
respectively.
Earth wire shall be longer than the other wires as shown in the figure for the electrical safety in case of
o
the slipping out of the cord from the Holder (Clamper).
2
An isolating device must be connected to the power supply cable.
Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
o
Connect the approved polychloroprene sheathed power supply 1 cord (3 x 4.0 or 6.0 mm
o
supply 2 cord (3 x 4.0 mm
and to the other end of the cord to isolating device (Disconnecting means).
3
To avoid the cable and cord being damaged by sharp edges, the cable and cord must be passed through a
bushing (located at the bottom of indoor unit) before being connected to the terminal block. The bushing must
be used and must not be removed.
Connecting with external device (optional)
1
All connections shall follow to the local national wiring standard.
2
It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
3
Maximum output power of booster heater should be ≤ 3 kW. Booster Heater cord must be (3 x min 1.5 mm
of type designation 60245 IEC 57 or heavier.
4
Three-Way Valve shall be spring and electronic type. Valve cable shall be (3 x min 0.5 mm
designation 60245 IEC 57 or heavier, or similarly double insulation sheathed cable.
* note: - Should be CE marking compliance component.
- It should be directed to heating mode when it is OFF.
- Maximum load for the valve is 9.8VA.
5
Room Thermostat cable must be (4 or 3 x min 0.5 mm
sheathed cable.
6
Tank OLP cable must be (2 x min 0.5 mm
cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal
no. 13 and 14.
7
Tank Sensor shall be resistance type, please refer to Graph 5.1 for the characteristic and details of sensor.
Its cable shall be (2 x min 0.3 mm
sheathed or rubber-sheathed cable.
8
External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to
Diagram 5.2). Its cable must be (2 x min 0.5 mm
sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no. 17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
9
Must install Solar Connection PCB
Connection PCB's installation instruction for detail of installation.
10 Solar Three-way Valve cable shall be (3 x min 0.5 mm
sheathed cable.
11 Solar Pump Station cable shall be (2 x min 0.5 mm
cable. Strongly recommended install with maximum length of 10 meter only.
2
) and type designation 60245 IEC 57 or heavier cord to the terminal board,
2
), double insulation layer of PVC-sheathed or rubber-sheathed
2
), double insulation layer (with insulation strength of min 30V) of PVC-
2
), double insulation layer of PVC-sheathed or rubber-
(optional) to indoor unit when Solar Pump Station is utilized. Refer Solar
2
), of double insulation PVC-sheathed or rubber-sheathed
47
2
), double insulation layer of PVC-sheathed or rubber-
.
rms
2
), double insulation layer PVC-sheathed or rubber-
2
) and power
2
),
2
), of type