Summary of Contents for ABB ACS880-0P

  • Page 1 — ABB Drive Products ACS880-0P Sensia CE Supplemental Manual...
  • Page 2: Table Of Contents

    Table of Contents _____________________________________________________ Safety Instructions ………………………………………………………………………………..3 Introduction to the Supplement …………………………………………………………………... Mechanical Installation …………………………………………………………………………..Electrical Installation ……………………………………………………………………………….. Operation ……………………………………………………………………………………………... 20 Maintenance Schedule ……………………………………………………………………………... 21 Appendix A …………………………………………………………………………………………… 22...
  • Page 3: Safety Instructions

    Warnings tell you about conditions which can cause injury or death, or damage to the equipment. They also tell you how to prevent the danger. Notes draw attention to a particular condition or fact, or give information on a subject. The manual uses these warning symbols: ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 4 19.17 Local control disable has value Disabled), the stop key on the control panel will not stop the drive. • Do not attempt to repair a malfunctioning drive; contact your local representative for replacement or repair by authorized persons. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 5 These functions reset the drive automatically and continue operation after a fault. Note: When the control location is not set to Local, the stop key on the control panel will not stop the drive ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 6 DC terminals (UDC+ and UDC-) and the grounding (PE) terminal is zero. 6. Install temporary grounding as required by the local regulations. 7. Ask from the person in control of the electrical installation work for a permit to work. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 7 If you have a cardiac pacemaker or other electronic medical device, keep away from the area near motor, drive, and the drive power cabling when the drive is in operation. There are electromagnetic fields present which can interfere with the function of such devices. This can cause a health hazard. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 8 In addition, • install a second protective earth conductor of the same cross-sectional area as the original protective earthing conductor, • install a protective earth conductor with a cross-section of at least 10 mm2 Cu ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 9 ABB and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 10: Introduction To The Supplement

    You are expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. Purpose of the document This supplement provides technical data and other information for the ACS880-0P, 380/400/415V 50/60Hz. drives. Complete base drive technical details are available in the ACS880 Hardware manual frames R1 to...
  • Page 11 ACS880-01 quick installation guide for frames R6 to R9 3AUA0000099689 Manuals and other product documents in PDF format are available on the Internet. For manuals not available in the Document library, contact your local ABB representative. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 12: Mechanical Installation

    Verify there are no signs of damage. Before attempting installation and operation, check the information on the type designation labels of the drive to verify that the delivery is of the correct type. Required tools ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 13 A 6 ft “spreader beam” using (4) 6 ft straps is recommended for lifting the R11 enclosure. A 1-Point lift using (4) 6 ft straps has been analyzed to be safe but is not the recommended method of lifting. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 14 A 6 ft “spreader beam” using (4) 4 ft straps is recommended for lifting the (2)R11 enclosure. Moving the cabinet after unpacking Move the drive cabinet carefully in the upright position. Avoid tilting. The cabinet’s center of gravity can be high. Installing the drive ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 15 The cabinets are free standing and do require bolting in place. Leave some space at the side to allow doors to open sufficiently. The doors can open 120°. ABB recommends minimum of 3 feet side to side spacing and 5 feet clearance on the back (see images below).
  • Page 16: Electrical Installation

    The connections points vary depending on the size of units and the option selected, Power Junction Box (+H361) or Harmonic Junction Box (+H384). The following figures show the layout and connection points. Maintain appropriate separation of control and power wires. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 17 R9 Enclosure, No Junction Box R11 Enclosure, No Junction Box R9 or R11 Enclosure, Power Junction Box (+H361) R11 Enclosure, Harmonic Junction Box (+H384) ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 18 R9 Enclosure, Harmonic Junction Box (+H384) (2)R11 Enclosure, No Junction Box ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 19 Power blocks are rated for 800Amps each. NOTE: With the customer supplied and installed harmonic filter, to maintain the 100kA SCCR rating the harmonic filter must have a 100kA SCCR and be installed per the manufacturer’s recommendations. ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 20: Operation

    Sequence of operation per the customer. The Instruct controller is programmed to control the drive. Note: The Service Outlet (SO) Ethernet port is a maintenance/ diagnostic port. Only connect ABB keypad to Ethernet port for drive diagnostics. Power outlet 100VA max intended for computer supplies only.
  • Page 21: Maintenance Schedule

    ACS880-04FXT Hardware Manuals for fan replacement instructions. See the enclosure filter fan manual for replacement instructions. Years From Start-Up Component 3 5 6 9 10 Main Drive Cooling Fan (R7 – R11) Auxiliary Cooling Fan Control Panel Battery Enclosure Filter Fans R = Replace ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 22 Cubicle-Type Assemblies External Design No IK Rating Declared Mechanical Impact Protection Fixed Parts Type of Construction Nature of Short-Circuit Protective 100kA at 480VAC Device(s) Measures for Protection Against Electric Protective Earthing Plus Basic Insulation Shock ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 23 Other Characteristics Pollution Degree TNC Network Type of System Earthing Outdoor Installation Type Stationary Stationary or Movable IP54 Degree of Protection Intended For Use By Skilled or ordinary Skilled Persons Electromagnetic Compatibility (EMC) Class A Classification ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 24 5 … 95% Atmospheric Conditions (Humidity) No condensation allowed. Maximum allowed relative humidity is 60% in the presence of corrosive gases. -40 … +70 Storage Temperature (°C) -15…+50 Operating Temperature (°C) Derate above 1000m Altitude ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 25 ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...
  • Page 26 ABB Inc. 16250 West Glendale Drive New Berlin, WI 53151 Telephone +1 262 785-3200, option 1 +1 262 785-0397 Internet www.abb.com/drives ACS880-0P SENSIA CE SUPPLEMENT [3AXD50000905423]...