Mitsubishi Electric FR-F802 Instruction Manual page 37

Separated converter type
Table of Contents

Advertisement

Control circuit
Safety stop signal
For the safety stop function, refer to
Terminal
Terminal name
Symbol
Safety stop input
S1
(Channel 1)
Safety stop input
S2
(Channel 2)
Safety stop input
SIC
terminal common
Safety monitor output
SO
Open collector output
Safety monitor output
SOC
terminal common
36
INSTALLATION AND WIRING
page
45.
Terminal function description
The terminals S1 and S2 are used for the safety stop input signal for the
safety relay module. The terminals S1 and S2 are used at the same time
(dual channel).
Inverter output is shutoff by shortening/opening between terminals S1
and SIC, or between S2 and SIC.
In the initial status, terminal S1 and S2 are shorted with the terminal PC
by shorting wires. The terminal SIC is shorted with the terminal SD.
Remove the shorting wires and connect the safety relay module when
using the safety stop function.
Common terminal for terminals S1 and S2.
Indicates the safety stop input signal status.
Switched to LOW when the status is other than the internal safety circuit
failure. Switched to HIGH during the internal safety circuit failure status.
LOW is when the open collector output transistor is ON (conducted).
HIGH is when the transistor is OFF (not conducted).
Refer to the Safety stop function instruction manual (BCNA23228-001)
when the signal is switched to HIGH while both terminals S1 and S2 are
open. (Please contact your sales representative for the manual.)
Common terminal for terminal SO.
Rate Specification
Input resistance
4.7 k
Input current 4 to 6
mADC (with 24 VDC
input)
———
permissible load
24 VDC (27 VDC at
maximum), 0.1 A
(The voltage drop is
3.4 V at maximum
while the signal is ON.)
———