Mitsubishi Electric FR-F802 Instruction Manual page 47

Separated converter type
Table of Contents

Advertisement

Control circuit
Connection diagram
To prevent restart at fault occurrence, connect terminals SO and SOC to the reset button, which are the feedback input
terminals of the safety relay module.
RESET
Emergency
stop button
Safety relay module
/ Safety programmable controller
Safety stop function operation
Input
Internal safety
power
circuit status
OFF
-
Normal
Normal
Normal
Normal
ON
Fault
Fault
Fault
Fault

ON: The transistor is conducted. OFF: The transistor is not conducted.

When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter. (In the initial status,
terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)

If any of the protective functions shown in the following table is activated, the terminal SO turns OFF.
Fault record
Option fault
Communication option fault
Parameter storage device fault
Retry count excess
Parameter storage device fault
Operation panel power supply short circuit
RS-485 terminals power supply short circuit

If the internal safety circuit is operated normally, the terminal SO remains ON until E.SAF is displayed, and the terminal SO turns OFF when E.SAF is displayed.

SA is displayed when the terminals S1 and S2 are identified as OFF due to the internal safety circuit failure.

If another fault occurs at the same time as E.SAF, the other fault can be displayed.

If another warning occurs at the same time as SA, the other warning can be displayed.
For more details, refer to the Safety Stop Function Instruction Manual (BCN-A23228-001).
Find a PDF copy of this manual in the CD-ROM enclosed with the product.
It is also can be downloaded from the Mitsubishi Electric FA Global Website.
http://www.mitsubishielectric.co.jp/fa/
46
INSTALLATION AND WIRING
SO
SOC
+24V
Fuse
PC
S2
S1
SIC
SD
Input terminal
,


S1
S2
-
-
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
Operation panel
indication
E.OPT
E.OP1
E.PE
E.RET
E.PE2
E.CTE
Inverter/ Converter unit
Logic
ASIC
CPU
Output
terminal
Inverter running status
SO
Output shutoff (Safe state)

Operation enabled
Output shutoff (Safe state)


Output shutoff (Safe state)
Output shutoff (Safe state)

Output shutoff (Safe state)
Output shutoff (Safe state)
Output shutoff (Safe state)
Output shutoff (Safe state)
Fault record
24 VDC power fault
Safety circuit fault
Overspeed occurrence
CPU fault
Internal circuit fault
R/L1 S/L2 T/L3
IGBTs
Gate
Gate
Driver
Driver
G
G
U V W
M
Operation panel indication
E.SAF

Not displayed
Not displayed
Displayed
Displayed
Not displayed
Displayed
Displayed
Displayed
Displayed
Operation panel
E.P24
E.SAF
E.OS
E.CPU
E.5 to E.7
E.13
SA

Not displayed
Not displayed
Displayed
Displayed
Displayed
Not displayed

Displayed
Displayed
Displayed
indication