Huawei NetCol5000-A050 Quick Manual page 18

In-row air cooled smart cooling
Hide thumbs Also See for NetCol5000-A050:

Advertisement

Connecting the Power Cable and Signal Cable for the Water-Cooled Module
Water-cooled module
power cable on the
side of the indoor unit
Water-
cooled
module
9.3
Connecting T/H Sensors Outside Cabinets
1. Connect the T/H sensor cables.
The T/H sensors in the aisles should be
installed on the door frame of IT cabinets,
and 1.5 m (33 U) away from the ground.
After the sensor is secured, set the sensor
address according to the following table.
2. Set the DIP switches on the T/H sensors.
Name
Cold aisle 1 temp/humid
Cold aisle 2 temp/humid
Cold aisle 3 temp/humid
Cold aisle 4 temp/humid
Cold aisle 5 temp/humid
Hot aisle 1 temp/humid
Hot aisle 2 temp/humid
Hot aisle 3 temp/humid
Hot aisle 4 temp/humid
Hot aisle 5 temp/humid
Power cable hole
Address
1
11
ON
12
OFF
13
ON
14
OFF
15
ON
21
ON
22
OFF
23
ON
OFF
24
ON
25
18
Signal cable hole
Signal cables for
the indoor units
Water-cooled
module
DIP Switch ID
2
3
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
4
5
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
6