Precautions When Wiring Com Port; Gt01 (5 V Dc) - Panasonic GT32-R User Manual

Programmable display
Table of Contents

Advertisement

3.4 Precautions when Wiring COM Port

Precautions are different depending on communication conditions. Arrange wirings according to the
following instructions.

3.4.1 GT01 (5 V DC)

RS232C type
Perform wiring and placement of the cable so that there is no impression of external noise on the cable
-
and no induction.
Use shielded wires for distribution cables.
-
(Recommended cable: AIGT8142 with one ferrite core)
It conforms to CE marking. As conditions, the following wiring is required.
-
1. Make the cable do three turns around a ferrite core.
(Recommended ferrite core: Seiwa Electric's E04RA190120080 or equivalent)
2. Perform grounding of the cable shield.
* Packaged with AIGT8142.
RS422 (RS485) type
There is no RS and CS (control lines).
-
Perform wiring and placement of the cable so that there is no impression of external noise on the cable
-
and no induction.
Use shielded wires for distribution cables.
-
(Recommended cable: AIGT8152 with one ferrite core(Seiwa Electric's E04RA190120080))
When using shielded cable with crossover wiring for the RS485 transmission line, grounded one end.
-
"E" is used to set the terminating station.
-
It does not conform to European EMC directive.
-
Key Point:
The CE marking standards that the GT01 conforms to (excluding the RS422 (RS485) type)
European EMC directive 2004/108/EC
European EMC standards (EN61000-6-4 and EN61000-6-2)
3-14

Advertisement

Table of Contents
loading

Table of Contents