Replacing the RTC Battery

The real-time clock is backed up by a lithium coin cell battery, IC690ACC001. The RTC battery has
an estimated life of 5 years and must be replaced every 5 years on a regular maintenance
schedule. There are no diagnostics or indicators to monitor RTC battery status.
If the RTC battery fails, the CPU date and time is reset to 12:00 AM, 01-01-2008 at startup. The
CPU operates with a failed or missing RTC battery; however the initial CPU TOD clock information
will be incorrect.
You will need the following:
GFK-2785C
To avoid damage from electrostatic discharge, adhere to the following
precautions when opening the IPC enclosure:
Wear a properly functioning antistatic strap and be sure that you are fully
grounded. Never touch any components inside the IPC unless you are
wearing an antistatic strap.
The IPC should be placed on a static-safe surface, facilitated by
antistatic mats.
Extra caution should be taken in cold, dry weather, when static charges
can easily build up.
One flat (or large Phillips) screwdriver
One small Phillips screwdriver
IC690ACC001 battery
1. Remove power from the IPC by disconnecting the power cable.
2. Loosen the four captive screws on the IPC's front panel and remove the front panel.
3. Remove the IPC from its mounting location and place it on a static-safe surface.
4. Remove the four Phillips-head screws that secure the interior lid to the IPC chassis, then
lift off the interior lid.