Hitachi Relion 670 Series Product Manual page 82

Phasor measurement unit
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Phasor measurement unit RES670
Version 2.2
Table 103. Voltage measurement phase-earth VNMMXU
Function
Voltage
Phase angle
Table 104. Current sequence measurement CMSQI
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Table 105. Voltage sequence measurement VMSQI
Function
Voltage positive sequence, U1
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
Table 106. Supervision of mA input signals
Function
mA measuring function
Max current of transducer to
input
Min current of transducer to
input
Alarm level for input
Warning level for input
Alarm hysteresis for input
82
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
Range or value
(5 to 175) V
(5 to 175) V
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5
Range or value
(0.1–4.0) × I
r
(0.1–1.0) × I
r
(0.1–1.0) × I
r
(0.1–4.0) × I
r
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
Range or value
±5, ±10, ±20 mA
0-5, 0-10, 0-20, 4-20 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
© 2017 - 2022 Hitachi Energy. All rights reserved
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
Accuracy
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±1.0 degrees at 0.1 × I
r
±0.5 degrees at 0.5 × I
r
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
M16080-1 v5
Accuracy
±0.1 % of set value ±0.005 mA
1MRK 511 410-BEN P
r
r
r
r
r
r
< I ≤ 0.5 × I
r
< I ≤ 4.0 × I
r
Hitachi Energy

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670