SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual
Item
Maximum output
current
Power factor
Maximum total
harmonic
distortion (rated
power)
Note a: The rated output voltage is determined by Grid code, which can be set on the SUN2000
app, SmartLogger, or NMS.
Note b: You can determine whether to connect the neutral wire to the SUN2000-115KTL-M2,
SUN2000-110KTL-M2, SUN2000-100KTL-M2, or SUN2000-100KTL-INM2 based on the application
scenario. If no neutral wire is used, set Output mode to Three-phase three-wire. If the neutral
wire is used, set the Output mode to Three-phase four-wire.
Protection
Item
SUN2000-115KTL
-M2
AFCI
-
Input DC
Supported
switch
Anti-
Supported
islanding
protection
Output
Supported
overcurrent
protection
Input
Supported
reverse
connection
protection
PV string
Supported
fault
detection
DC surge
Supported
protection
Issue 02 (2022-06-30)
SUN2000-115KT
SUN2000-110KT
L-M2
L-M2
182.3 A (400 V)
185.7 A (380 V)
and 151.9 A (480
and 176.4 A (400
V)
V)
0.8 leading and 0.8 lagging
< 3%
SUN2000-110KTL-
M2
-
Copyright © Huawei Technologies Co., Ltd.
10 Technical Specifications
SUN2000-100KT
L-M2
168.8 A (380 V),
160.4 A (400 V)
and 133.7 A (480
V)
SUN2000-100KTL-
M2
Supported
SUN2000-100KT
L-INM2
154.6 A (415 V),
133.7 A (480 V)
SUN2000-100KT
L-INM2
-
112