Water Heat Exchanger Unit
(3) Installing refrigerant piping and charging with refrigerant
Caution
!
Always replace the refrigerant with nitrogen before brazing refrigerant piping.
Loose oxide scales can cause motorized valves to seize and clog strainers, which can result in operation
failure.
1. Be sure to heed the caution labels on the water heat exchanger unit.
2. Pipe routes should be designed to use the shortest possible length of piping and for the minimum possible
difference between high and low points. When bending pipes, be careful to avoid kinking or fl attening.
3. Table 1 shows the limitations on refrigerant pipe length between the water heat exchanger unit and the
outdoor unit, and on the difference in height between the high and low points. Also add the unit additional
charge amount in Table 2 according to the outdoor unit type.
Table 1 Allowable refrigerant piping length, amount of refrigerant additionally charged, and pipe specifi cations
Allowable
Type
pipe length
Type
710
170m
Type
(equivalent
500
length 200m)
Type
250
* For cooling operation where the outdoor air temperature is 10°C or less, this value should be 30m.
• If the pipe length is 90m or more, use one size bigger one provided in parentheses.
Table 2 Unit additional charge amount
Outdoor unit type
Unit additional charge amount
4. Do not allow dust, dirt, or moisture to become trapped inside the piping.
5. After connecting the piping, perform gas leakage testing by means of an air purge (Figure 4).
Leakage testing may be legally required in accordance with local regulations such as the High Pressure
Gas Safety Law (in Japan). After connecting the pipes, perform testing in accordance with the points below
(or those for the installation locale), to confi rm that there are no leaks from the joints.
Cautions
1) Gas pressure in the gas leakage test: F4.15
MPa
2) After the gas leakage test, evacuate the system
to 667 Pa (-755 mmHg, 5 Torr).
3) Do not open outdoor unit valves until the gas
leakage and vacuum tests are complete.
4) Do not allow the equipment to sit idle for long
after completing vacuum testing.
6. Apply thermal insulation to the piping.
Apply the thermal insulation after completing
the leak check on the pipe joints.
Apply thermal insulation to both the thick
pipes and thin pipes.
7. A gas heat pump air conditioning system must be
installed in accordance with the "High pressure gas
safety law", the "Refrigeration safety regulations",
the "Criteria for refrigeration installations" published
by the High Pressure Gas Safety Institute of Japan,
and all the necessary reporting procedures must be
carried out.
GHP Chiller TECHNICAL DATA.indb   A-22
GHP Chiller TECHNICAL DATA.indb   A-22
Allowable height difference
When outdoor
When outdoor
unit is higher
unit is lower
50m
*35m
45.0 kW
56.0 kW
0.5 kg
A-22
6. Installation considerations
Amount of additional
Refrigerant piping (copper pipe C1220T,
refrigerant
external diameter × wall thickness in mm)
For the length of
Liquid side
refrigerant piping
(O-material)
Ø19.05×1.0
259g/m (366g/m)
(Ø22.22×1.0)
Ø15.88×1.0
185g/m (259g/m)
(Ø19.05×1.0)
Ø9.52×0.8
56g/m (128g/m)
(Ø12.7×0.8)
71.0 kW
85.0 kW
2.5 kg
10.0 kg
Gas side
(1/2H, H-material)
Ø31.75×1.1
(Ø38.1×1.35)
Ø28.58×1.0
(Ø31.75×1.1)
Ø22.22×1.0
(Ø25.4×1.0)
2012/04/06   13:42:06