Technical specifications

The following table shows the technical specifications as of 05/2021. You will find a data
sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/ww/en/pv/6ES7511-1AK02-0AB0/td?dl=en).
Article number
General information
Product type designation
HW functional status
Firmware version
Product function
I&M data
Isochronous mode
Engineering with
STEP 7 TIA Portal configurable/integrated
from version
Configuration control
via dataset
Display
Screen diagonal [cm]
Control elements
Number of keys
Mode buttons
Supply voltage
Type of supply voltage
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Mains buffering
Mains/voltage failure stored energy time
Repeat rate, min.
Input current
Current consumption (rated value)
Current consumption, max.
Inrush current, max.
I²t
Power
Infeed power to the backplane bus
Power consumption from the backplane bus
(balanced)
Power loss
Power loss, typ.
38
6ES7511-1AK02-0AB0
CPU 1511-1 PN
FS03
V2.9
Yes; I&M0 to I&M3
Yes; Distributed and central; with minimum OB 6x
cycle of 625 µs (distributed) and 1 ms (central)
V17 (FW V2.9) / V15 (FW V2.5) or higher; with
older TIA Portal versions configurable as 6ES7511-
1AK01-0AB0
Yes
3.45 cm
8
2
24 V DC
19.2 V
28.8 V
Yes
5 ms
1/s
0.7 A
0.95 A
1.9 A; Rated value
0.02 A²·s
10 W
5.5 W
5.7 W
CPU 1511-1 PN (6ES7511-1AK02-0AB0)
Equipment Manual, 05/2021, A5E40869673-AB
5

Advertisement

Table of Contents
loading