NO.0764E RAS-PH18PHLAE / RAC-PH18WHLAE RAS-PH24PHLAE / RAC-PH24WHLAE WALL TYPE TYPE INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT MODEL RAS-PH18PHLAE RAC-PH18WHLAE RAS-PH24PHLAE RAC-PH24WHLAE POWER SOURCE 1 PHASE 60Hz 208-230V TOTAL INPUT 1325 1650 (W) TOTAL AMPERES 5.80 7.20 (A) COOLING (KW)...
Page 58
RESISTOR RESISTOR CAPACITOR DIODE VALUE ASSY. VALUE ASSY SYMBOL TOLERANCE WATT FORM GROUP REMARK SYMBOL TOLERANCE WATT FORM GROUP REMARK (Ω) (Ω) VALUE FORM GROUP ASSY R001 R651 1/16 A , B 1005 ASSY SYMBOL MODEL SYMBOL VOLTAGE TYPE FORM GROUP REMARK µ...
Page 76
Operates when the following conditions are met When the clean operation start time or the last stop time is reached during stop * It does not work at the time stopped by the off timer. Judge room temp. & outdoor tem Elapsed after setting Room temp.
Page 77
Prohibition conditions Integration time When the time until the on timer starts is within 120 minutes. Counts the time since the outdoor unit frost wash was set. If you cancel the outdoor unit frost wash, it will be reset. Resets when the first freeze period begins. Cancellation condition Conditions for early termination When the the outdoor unit frost wash is canceled.
Page 78
Outdoor unit fan reverse rotation It works when the outdoor unit frost wash is set. Start condition If it operates for 10 minutes or more and stops, the reverse rotation will operate every time. It operates even if it is stopped by a timer. Conditions for early termination When operation is started.
Page 112
Other instructions (1) Detaching and reattaching the receptacles for tab terminal All the receptacles for connecting tab terminals are with a locking mechanism. Forcibly pulling any such receptacle without unlocking it will destroy it. Be on guard. When reconnecting it, insert it securely all the way home. ・Receptacle types and how to unlock them Mild resin cover Cancel button...
Troubleshooting support Function Self-diagnosis display ・The failure mode detected on the indoor unit side is displayed by [Display on the indoor blinking the "timer lamp". And a failure detected on the outdoor unit side] unit side will be indicated by the "time lamp" blinking 4 times. ・If the outdoor unit side detects a failure, the product will first conduct several operation retrials.
Page 119
While pressing and holding (ON/OFF) button and button, press [RESET] button on the same. Release [RESET] button only and make sure that all marks on the remote controller display are indicated then release the (ON/OFF) button and button. Remote controller now enters "Shift Value Change Mode". Press the (MODE) selector button so that the display indicates (FAN) mode.
Page 120
a.) Other indoor circuit breakers should be disconnected. b.) Remove the back cover of the remote control. c.) Cut the jumper as shown below. d.) Press “Reset” button after installing the battery. e.) Corresponding to the room electrical box dial code 6 to dial on. Cut (Attention: Remove the battery before cutting.
Page 121
HOW TO CHANGE THE FAN SPEED IN COOLING MODE DURING THERMO OFF The fan speed in Cooling Mode during thermo off can be changed by the remote controller. (This procedure shall be implemented strictly by service personnel only.) It is possible to return it to the default setting. PROCEDURE Press [POWERFUL] button and...
Page 122
HOW TO CHANGE THE The intermittent fan control during thermo off in Heating mode can be changed by the remote controller. (The procedure should be done only by service personnel.) It is possible to select from 3 patterns. PROCEDURE Press (POWERFUL) button, (FAN SPEED) button and press [RESET] button simultaneously.
Page 123
(ON/OFF) button and While pressing and holding (UP/DOWN) button, press ( RESET) button on the same time. Release (RESET) button only and make sure that all marks on the LCD display are indicated, then release the (ON/OFF) button and (UP/DOWN) button.
Page 130
3. Failure phenomenon: The compressor will not run. [ Situation ] The compressor will not run (the same state as the thermometer turned off), the product receives remote control signals normally. The self-diagnosis lamp (LD301) of the outdoor unit blinks once or becomes turned off. [ Estimated failure locations ] ・Room temperature thermistor, heat exchanger thermistor ・Microcomputer peripheral circuit [ Diagnosis flow ]...