Softstarters
Type PSE
Fieldbus Communication
Fieldbus Plug Modbus TCP
1SFC132374M0201
January 2019

Advertisement

Table of Contents
loading

Summary of Contents for ABB PSE

  • Page 1 Softstarters Type PSE Fieldbus Communication Fieldbus Plug Modbus TCP 1SFC132374M0201 January 2019...
  • Page 2 ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 3: Table Of Contents

    Technical Description ............................. 4 Modbus TCP ............................4 MTQ22-FBP ............................5 Connection Setup ........................... 6 Software Configuration ..........................7 PSE Softstarter ............................7 MTQ22-FBP ............................10 Modbus TCP Register Map .......................... 14 Digital Input Telegram ........................14 Digital Output Telegram ........................16 Analog Input Telegram ........................
  • Page 4: Overview

    IP network. The use of IP datagrams removes the need for slave addresses since all slaves use a unique IP address to enable IP communication. However, The MTQ22-FBP still uses Modbus RTU to communicate with the PSE which require the slave ID to match between the MTQ22-FBP and the PSE, as explained in section 3.2.
  • Page 5: Technical Description

    The following list highlights the core features and functionalities provided by the MTQ22-FBP and Modbus TCP protocol. Highlighted Features  The MTQ22-FBP Ethernet adapter module provides Ethernet connectivity for the ABB PSE softstarter Fieldbus plug (FBP) device.  Up to four FBP devices can be connected to one MTQ22-FBP. This allows a very cost-efficient connection of FBP devices to Ethernet.
  • Page 6: Mtq22-Fbp

    See chapter 5 for detailed information regarding status LEDs. Figure 1: Top view of the MTQ22-FBP. Four PSE devices can be connected to the MTQ22 via the ports X1 to X4. The standard Micro USB connector X5 allows to configure the device.
  • Page 7: Connection Setup

    X1 to X4 on the MTQ22-FBP. The Modbus master is in turn connected to one of the Ethernet connections E1 or Figure 2: Device connections required to enable a Modbus TCP connection between the PSE and a Modbus master. The cable connecting the PS-FBPA and the MTQ22-FBP, a CDP19-FBP .100 cable must be purchased separately.
  • Page 8: Software Configuration

    This chapter describes how to configure the MTQ22-FBP and the PSE to enable Modbus communication. 3.1 PSE Softstarter The following list of instructions explains how to configure the fieldbus parameters on the PSE softstarter. Fieldbus Control This parameter is used for configuration of the fieldbus communication. Connecting the PSE Softstarter to the Fieldbus plug automatically enables fieldbus communication.
  • Page 9 The fieldbus type parameter must be set to FbP (fieldbus plug) when using the MTQ22-FBP. FbP is the default value of the parameter. The PSE has a built-in version of Modbus which is activated by setting the parameter to Int (Internal).
  • Page 10 Fieldbus Operation When Fault This parameter is accessible only if Fieldbus Control is previously set to On. In case of fieldbus malfunction, for instance due to power loss or a broken cable, this parameter allows for different (operations in case of a fault) reactions to the fault. Setting Fieldbus fault reaction to trIP will make the softstarter trip on a fieldbus fault.
  • Page 11: Mtq22-Fbp

    An easy to use PC configuration tool is provided to adjust the parameters of the MTQ22-FBP. The PC can be connected to the MTQ22-FBP with a standard Micro USB-cable. The ABB Configuration Tool can be downloaded by clicking the following link or searching for 1SAJ260900R0001 at the ABB Download Center.
  • Page 12 Set required MTQ22-FBP parameters The following steps describes how to set the required parameters on the MTQ22-FBP. After the application is started (as administrator) select the MTQ22-FBP that you want to configure in the Config Tool. From the Select port drop down menu select the COM port associated to the MTQ22-FBP and click connect.
  • Page 13 Device port 1 ... 4 used Device address for device 1 ... 4 1,2,3,4 Select the connected FBP device and chose PSE in the drop-down menu called Expected device. For the ports without a connected device chose Port not used. 1SFC132374M0201...
  • Page 14 MTQ22-FBP. When the two Device addresses match for all connected PSEs click the Write to MTQ22-FBP button again. Note that, when the slave ID is updated in the PSE a reboot will be required on the PSE for the Config Tool to the detect the new value.
  • Page 15: Modbus Tcp Register Map

    Depending on your client application it might be necessary to increment all addresses by one. The I/O-data as well as diagnostic and configuration data of the connected PSE devices can be accessed applying the supported Modbus function codes. The supported functions can be found in respective sub section.
  • Page 16 100Ch 101Ch 102Ch 103Ch DI_Stop Hardwire DI Stop input signal state 0 = DI Stop signal inactive 1 = DI stop signal active 100Dh 101Dh 102Dh 103Dh DI_Reset Hardwire DI Reset input signal state 0 = DI Reset signal inactive 1 = DI Reset signal active 100Eh...
  • Page 17: Digital Output Telegram

    4.2 Digital Output Telegram To write the digital output telegram, use Modbus function code 5 Write Single Coil or 15 (0Fh) Force Multiple Coils. To read the digital output telegram, use Modbus function code 1 Read Coil Status or 2 Read Input Status. Address for data access to device connected to port Data Description...
  • Page 18: Analog Input Telegram

    Value = 1 ⇒ 10h 200Ah 210Ah 220Ah 230Ah Run time in hours 4.4 Parameters The MTQ22-FBP does not support reading or writing PSE softstarter parameters such as start ramp time, initial voltage and torque control. 1SFC132374M0201...
  • Page 19: Diagnostics

    PSE Softstarter PSE softstarter diagnostics are represented by bits in a 16-unsigned integer register. Use a calculator to translate the decimal number to one or more bits. If a bit is set that fault is active and could potentially be resetted.
  • Page 20 Bad network quality Bad network quality on the line side Current loss Current is not flowing when it should Fieldbus fault Fieldbus communication failure Low supply voltage Too low control supply voltage High current Too high current Motor overload Too high motor temperature Locked rotor protection Current is higher than settable value during top of...
  • Page 21: Mtq22-Fbp Led Diagnostics In Case Of Error

    5 MTQ22-FBP LED Diagnostics in Case of Error Diagnostic information is locally displayed using two Light Emitting Diodes (LEDs) per PSE device interface. The meaning of the LEDs is as follows. Explanation Port 1, 2, 3, 4 Disabled (no device configured)
  • Page 22: Basic Tcp Modbus Diagnostic Information

     If the Reset of Fieldbus Fault PSE parameter is set to Auto and the fieldbus fault (EF40) has tripped due to no communication, 30 s of stable communication is required before an automatic reset is performed.