Press Enter to access the different settings corresponding to the F49 function: TRIP49, TAP49, ALARM49, T1 and
T2. Pressing "+" and "-" move through these settings headings until the display shows the one you want to change.
Select it by pressing Enter. At this point, the actual value for that setting is shown, blinking. Pressing "+" and "-"
change this value to the appropriate one. Press Enter and the relay will ask for your confirmation. To confirm the
change press Enter.
The mnemonics in figure 8.11 stand for:
TRIP 49
TAP 49
ALARM 49
T1
T2
CNF
8.6
ADVANCED SETTINGS MENU
The display and keypad use for the Advanced Settings is as follows:
Figure 8.12. KEYPAD AND DISPLAY HANDLING FROM ADVANCED SETTINGS
Press Enter to access the different settings corresponding to the General Advanced Settings: TAB and TRIP MIN
TIME. Pressing "+" and "-" move through these settings headings until the display shows the one you want to change.
Select it by pressing Enter. At this point, the actual value for that setting is shown, blinking. Pressing "+" and "-"
change this value to the appropriate one. Press Enter and the relay will ask for your confirmation. To confirm the
change press Enter.
GEK-106273L
KEYPAD AND DISPLAY
Permission to Trip
49 Current Pickup
49 Alarm Threshold
Heating Time Constant
Cooling Time Constant
CONFIRM
TAB
ESC
ESC
ENTER
MIF Digital Feeder Protection
Range: Y / N.
Range: 0.10 to 2.40 x In
Range: 70 to 100% ITH
Range: 3 to 600 min
Range: 1 to 6 times T1
OK
Validate the value selected.
TRIP MIN TIME
+
ENTER
VALUE
ENTER
CNF
ENTER
OK
Step: 0.01 x In.
Step: 1.
Step: 1 min.
Step: 1.
8-19