The mnemonics used are:
DATE TIME
YXX (YEAR)
MXX (MONTH)
DXX (DAY)
HXX (HOUR)
MXX (MINUTE)
DATE AND TIME
8.9
RESETTING THE THERMAL IMAGE UNIT
To reset the Thermal Image Unit using the faceplate keypad and display follow the flow chart shown in figure 8.13.
Look for the RST THERMAL heading in the display. Press Enter. A confirmation message will be shown, CNF. To
confirm that you really want to reset the Thermal Image Unit press Enter. The thermal Image unit will be reset and
the message OK will be shown to point out that the operation has been executed successfully. To return to the
second level press Enter, as figure 8.13 indicates.
It is also possible to reset the Thermal Image Unit from the computer, using the ENERVISTA MII SETUP program.
Enter in the Operations Menu of the ENERVISTA MII SETUP program and select the corresponding button.
8.10
RESETTING THE TARGET LEDS
There are three ways to reset the faceplate target LEDs using the relay keypad:
1. Starting from the Steady State scrolling display press Enter for more than three seconds. All LEDs will light up
(LEDs test) and reset. To check that all LEDs are operative, press Enter and release it before three seconds. By
doing that, all LEDs will light up but will not be reset.
2. Follow figure 8.13 and look for the RST LEDS message in the display. Press Enter. The confirmation message
will be shown CNF. Press Enter to confirm that you really want to reset the LEDs. All Target LEDs will be reset
and the message OK will be shown, to point out that the operation has been performed successfully. To return to
the second level, press Enter.
3. RESET LEDS digital input (in OPTION 1 and OPTION 2 models).
It is also possible to reset the Target LEDs from the computer, using the ENERVISTA MII SETUP program. Enter in
the Operations Menu of the ENERVISTA MII SETUP program and select the corresponding button.
GEK-106273L
KEYPAD AND DISPLAY
Relay Date and Time.
Set the Year Information in the relay internal clock.
Set the Month Information in the relay internal clock.
Set the Day Information in the relay internal clock.
Set the Hour Information in the relay internal clock.
Set the Minutes Information in the relay internal clock.
The Date and Time just set in the relay is shown.
MIF Digital Feeder Protection