Io Input Image Data - 10Byte - Hitachi HX-RIO3 Series User Manual

Special i/o module
Hide thumbs Also See for HX-RIO3 Series:
Table of Contents

Advertisement

10
2.4 IO Input Image Data – 10byte
Bit No
Bit 7
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
-
Each channel has 4-byte Input
-
Counter value represents counter, frequency(Hz), pulse width (0.1usec) or pulse period (0.1usec).
(When IDS = 0)
-
IDS : Input Data Selection (Setting by Output Data)
-
Status Bit
The Status High can only read.
SUP : Status Counter Up
SDN : Status Counter Down
SAIN : Status A Terminal Input
SBIN : Status B Terminal Input
SGIN : Status G Terminal Input
Bit 6
Bit 5
Current Counter Value CH#0 LL when IDS = 0
Store Counter Value CH#0 LL when IDS = 1
Current Counter Value CH#0 LH when IDS = 0
Store Counter Value CH#0 LH when IDS = 1
Current Counter Value CH#0 HL when IDS = 0
Store Counter Value CH#0 HL when IDS = 1
Current Counter Value CH#0 HH when IDS = 0
Store Counter Value CH#0 HH when IDS = 1
Current Counter Value CH#1 LL when IDS = 0
Store Counter Value CH#1 LL when IDS = 1
Current Counter Value CH#1 LH when IDS = 0
Store Counter Value CH#1 LH when IDS = 1
Current Counter Value CH#1 HL when IDS = 0
Store Counter Value CH#1 HL when IDS = 1
Current Counter Value CH#1 HH when IDS = 0
Store Counter Value CH#1 HH when IDS = 1
SGIN
SBIN
CH#0
CH#0
SGIN
SBIN
CH#1
CH#1
Bit 4
Bit 3
SAIN
SDN
CH#0
CH#0
SAIN
SDN
CH#1
CH#1
HX-RIO3 Series
Bit 2
Bit 1
SUP
Out Status
CH#0
CH#0
SUP
Out Status
CH#1
CH#1
Bit 0
Inp Status
CH#0
Inp Status
CH#1

Advertisement