3.4 Firmware functions
The PROFINET interface X3 P1 is split internally for the CPU Runtime and the C/C++ Runtime.
Therefore, there is one IP address for the CPU and one IP address for the C/C++ Runtime.
• Set the IP address of the CPU in STEP 7.
You can find additional information in the online help for STEP 7.
• Set the IP address of the C/C++ Runtime in the configuration file of the C/C++ Runtime (see
the section "Initial commissioning").
Note the following restrictions when configuring the PROFINET interface X3 P1 with STEP 7:
• The configuration of the "Transmission rate/duplex" has no effect on the connection to the
PROFINET interface X3 P1 and the C/C++ Runtime.
• The "Monitor" option is not supported.
• Topology configuration is not supported.
Figure 3-3  Port options in STEP 7
NOTE
Availability of the X3 interface
Interface X3 is available only after approximately 1 to 2 minutes after POWER ON of the CPU.
Initial commissioning
Minimum requirement
SIMATIC memory card with a capacity of at least 2 GB.
Procedure
Proceed as follows to commission the C/C++ Runtime:
1. Start a Secure Shell Client (e.g. PuTTY).
2. Connect the Secure Shell Client to the CPU 1518(F)-4 PN/DP MFP using the PuTTY
configuration "CPU 1518MFP Linux Secure Connection" via the target address (default
address: 192.168.15.18).
3. Type in the user name and password and establish a Secure Shell Connection.
The default user name is "root". The default password is displayed under "Overview > MFP
> Default Password".
28
CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
Equipment Manual, 11/2022, A5E40882737-AC