Zone Assignments; Table 16: Zone Assignments - Bosch Solution 6000-IP CC615GWF Quick Start Manual

Hide thumbs Also See for Solution 6000-IP CC615GWF:
Table of Contents

Advertisement

Solution 6000-IP
Quick Start Guide
Zo n e Assign ment s
Address Setting
Module
Number
SW1 SW2 SW3 SW4 SW5
Control Panel
1 =
OFF OFF OFF OFF OFF
2 =
ON OFF OFF OFF OFF
3 =
OFF ON OFF OFF OFF
4 =
ON ON OFF OFF OFF
5 =
OFF OFF ON OFF OFF
6 =
ON OFF ON OFF OFF
7 =
OFF ON ON OFF OFF
8 =
ON ON ON OFF OFF
Inputs > Zone Properties >
Pulse Count
00 - No Pulse Count
01 - 1 Pulse
02 - 2 Pulses
03 - 3 Pulses
04 - 4 Pulses
05 - 5 Pulses
06 - 6 Inertia Pulses
07 - 7 Inertia Pulses
Enter 0 – 15 + [OK] to program the number of pulses the
zone must register within the zone pulse count time.
Inputs > Zone Properties >
Pulse Count Time
Enter value between 000 – 255 then select muliplier of
seconds, minutes or hours. Press [OK] to save. Use the
[←] and [→] keys to toggle between value and multiplier
settings.
30
Zone Assignment Table
Zone Numbers
(Single EOL)
(Alarm+Tamper EOL)
1 to 8
17 to 24
33 to 40
49 to 56
65 to 72
81 to 88
97 to 104
113 to 120
129 to 136

Table 16: Zone Assignments

MENU 3-1-3
Pulses
0 0
08 - 8 Inertia Pulses
09 - 9 Inertia Pulses
10 - 10 Inertia Pulses
11 - 11 Inertia Pulses
12 - 12 Inertia Pulses
13 - Door Open Too Long
14 - PreDelay
15 - Reserved
MENU 3-1-4
1 2 0
Seconds
Zone
Zone Numbers
Numbers
(Split EOL)
1 to 8
1 to 16
17 to 24
17 to 32
33 to 40
33 to 48
49 to 56
49 to 64
65 to 72
65 to 80
81 to 88
81 to 96
97 to 104
97 to 112
113 to 120
113 to 128
129 to 136
129 to 144
Inputs > Zone Properties >
Door Assignment
00 - Disabled
01 - Door 1 Name
02 - Door 2 Name
03 - Door 3 Name
04 - Door 4 Name
05 - Door 5 Name
06 - Door 6 Name
07 - Door 7 Name
08 - Door 8 Name
A single door can be assigned to each zone. Use the []
and [] keys to highlightdoor name, then press [OK] to
save.
Inputs > Zone Properties >
Report Route
00 - Log Events Only
01 - Dest 1 + Log
02 - Dest 2 + Log
03 - Dest 1 & 2 + Log
04 - Dest 2 If 1 Fails
Use [] and [] keys or enter 0 - 4 + [OK] to set the
destination zone reports are sent to.
Single or Alarm +
Tamper EOL With CM705B
+ CM707B Module
1 to 8
17 to 24
25 to 32 on the CM707B
33 to 40
41 to 48 on the CM707B
49 to 56
57 to 64 on the CM707B
65 to 72
73 to 80 on the CM707B
81 to 88
89 to 96 on the CM707B
97 to 104
105 to 112 on the CM707B
113 to 120
121 to 128 on the CM707B
129 to 136
137 to 144 on the CM707B
MENU 3-1-5
09 - Door 9 Name
10 - Door 10 Name
11 - Door 11 Name
12 - Door 12 Name
13 - Door 13 Name
14 - Door 14 Name
15 - Door 15 Name
16 - Door 16 Name
MENU 3-1-6
Bosch Security Systems 10/22 BLCC615R