Connection Data
If fork-type cable lugs or connector sleeves are used, the crimp zone must be insulated to
comply with the required insulating clearance. This can also be done using shrink-on sleeve.
The following data must be met:
Cable lugs for bolt diameter
max. major diameter
for cross-section from 1.0 mm
The cross-section on outputs 11 / 12 must be 2.5 mm
Use copper conductors only!
Recommended cable lugs series PIDG of Messrs. Tyco Electronics AMP, e.g.
ring-type cable lug
fork-type cable lug
Direct connection with solid bare wire or flexible wire with end sleeves;
for cross-section from 0.5 mm
When using one single conductor, the conductor end must be inserted such that it will be
drawn into the contact cavity while tightening the screw.
Use copper conductors only!
Wire strip length solid bare wire
max. torque value
16
4 mm;
10 mm;
2
2
to 2.6 mm
; resp. AWG 16 to AWG 14.
PIDG PN 320565-0,
PIDG PN 321233-0.
2
2
to 2.6 mm
; AWG 20 to AWG 14.
9 mm to 10 mm or 0.354 in or 0.394 in.
1.8 Nm or 16 in-lb.
7XT3300-0*A00/DD