Philips Dynalite Installation Manual page 15

Electrical & hardware
Hide thumbs Also See for Dynalite:
Table of Contents

Advertisement

Installing dry contact input devices
DLLI8I8O and DPMI940-DALI
Safety Note: DALI Dry Contact inputs are FELV (not touch safe) and they are galvanically connected to
A
the DALI network. ONLY Dry Contact switches with mains rated safety isolation shall be interfaced.
Refer to device installation instructions for cable length, safety insulation, requirements, and limitations.
1.
Install as close to the switching source as possible. This also applies to AUX/UL924 inputs on controllers.
Refer to the Installation Instructions for allowed cable lengths.
2.
DLLI8I80 has an RS-485 interface and can be connected to eight open/close contacts and eight indicator
LEDs.
3.
DPMI940-DALI has a DALI interface and can be connected to four open/close contacts
(must be used with a DDBC120-DALI controller).
DDMIDC8
Safety Note: Analog input circuits must be SELV/Class 2 (UL).
A
1.
Robust device recommended for locations with potential EMF noise, long cable runs up to 50 m (165 ft),
where additional optical isolation for dry contacts is required or for analog control integration.
2.
Can be installed without a DIN rail by extending DIN rail clips to expose mounting screw holes.
3.
If used, connect voltage-free contacts or 0-24V AC/DC inputs to any of the eight opto-isolated inputs.
Remove the cover and ensure that the internal jumpers for each input are set to the appropriate 0-24V or
voltage-free setting, according to the input type.
4.
Setting the internal jumper to the volt-free position increases the current consumption of the device from
15mA to 40mA. This must be considered when selecting DyNet data cable and supply capacity.
5.
If used, connect 0-5 V or 0-10 V inputs to the analog ports. Ensure the input is a maximum of 10 VDC.
Faders can be directly connected to the analog inputs by using the adjacent +5V terminal as a supply.
Suggested fader value is 10K ohm.
6.
Only draw a maximum of 25mA from the +5V terminal.