This UPS does not include an AC input circuit breaker (MCCB) to protect the
bypass and main input circuit. The AC input circuit breaker (MCCB) is to be
field supplied and installed.
specifications are as follows:
TABLE 1.2 Rating of AC input
Capacity
(kVA)
30
50
AC output and DC input overcurrent protection and disconnection devices shall be field
supplied and installed. Refer to the ratings of overcurrent protection device as indicated
"Breaker" in TABLE 1.6.
2033G SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 4
Recommended circuit breaker (MCCB)'s
circuit breaker
AC input
Voltage (Vac)
208
208
MITSUBISHI ELECTRIC 2033G SERIES UPS
AC input
Recommended
Rating (Aac)
Breaker (A)
85
142
Page Number:
1-4
125
200