  • Page 1 SMART 7KT0307 Manual MANUAL SMART 7KT Multifunction meter 7KT0307 (Single Line LED Class 1) SMART 7KT power monitoring devices...
  • Page 2 SMART 7KT0307 Manual Index SMART 7KT Introduction Multifunction meter Safety precautions 7KT0307 (Single Line LED Class 1) Technical specification Installation Connection Configuration Manual Communication Maintenance 09/2022 SME7KT030700...
  • Page 3: Purpose Of This Document

    SMART 7KT0307 Manual Introduction 1.1 Purpose of this document This present manual describes the SMART 7KT multifunction meter. It is intended for the use of: • Planners • Plant operators • Commissioning engineers • Service and maintenance personnel 1.2 Required basic knowledge A general knowledge of the field of electrical engineering is required to understand this manual. Knowledge of the relevant safety regulations and standards is required for installing and connecting the device. 1.3 Components of the product...
  • Page 4: Safety Precautions

    SMART 7KT0307 Manual Safety precautions DANGER Hazardous voltage will cause death or serious injury. Turn off and lock out all power supply before working on this device. NOTICE Installation and maintenance must be carried out by qualified personnel. This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances in which case the user may require to take adequate mitigation measures. Risk of damage: Please ensure the proper isolation of meter during the IR (Meggering) test.
  • Page 5: Technical Specification

    SMART 7KT0307 Manual Technical specification 7KT0307 (Single Line LED Class 1) Power Monitoring Device Panel instrument for std electrical values Protocol: Modbus RTU, Single line LED Display Vaux: 95V to 240V AC x/1 or 5 A, Class 1 Measurements measuring procedure • for voltage measurement True RMS • for current measurement True RMS type of measured value detection complete voltage curve Sinusoidal or distorted measurable line frequency • initial value 45 Hz • full-scale value 65 Hz operating mode for measured value detection automatic line frequency detection Supply voltage design of the power supply SMPS power supply type of voltage of the supply voltage Degree of protection class...
  • Page 6 • minimum -20 °C • maximum 75 °C relative humidity at 25 °C without condensation during operation 85 % maximum installation altitude at height above sea level maximum 2 000 m degree of pollution IEC Standards Certifications SMART 7KT multifunction meter conforms to IEC Description Standard standards, IPC electronics assembly standard and Accuracy IEC 61557-12; RoHS IEC 62053-21 | Active Energy EMC requirements IEC 61326-1 Degree of protection test (IP) IEC 60529 Safety requirements...
  • Page 7: Installation

    SMART 7KT0307 Manual Assembly Installation For installing the meter Prepare the panel cutout with proper dimensions as shown below. OUTLINE PANEL CUTOUT Dimensions (in mm) Dimensions (in mm)
  • Page 8: Wiring Guidelines

    SMART 7KT0307 Manual Installation Guidelines 1. This equipment, being built-in-type, normally becomes a part of main control panel and in such case the terminals do not remain accessible to the end user after installation and internal wiring. 2. Conductors must not come in contact with the internal circuitry of the equipment or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator. 3. Circuit breaker or mains switch must be installed between power source and supply terminals to facilitate power ‘ON’ or ‘OFF’ function. However this switch or breaker must be installed in a convenient position normally accessible to the operator.
  • Page 9: Typical Wiring Diagram

    SMART 7KT0307 Manual Connection Typical Wiring Diagram 3 Phase - 4 Wire 2 Phase - 3 Wire 3 Ø - 4 Wire, 3 CT’s and 3 PT’s 2 Ø - 3 Wire, 2 CT’s and 2 PT’s 3 Phase - 4 Wire (commonly used) 3 Phase - 3 Wire 3 Ø - 4 Wire, 3 CT’s 3 Ø - 3 Wire, 2 CT’s and 2 PT’s...
  • Page 10: Terminal Connections

    SMART 7KT0307 Manual Typical Wiring Diagram (Continued) 1 Phase - 2 Wire 1 Ø - 2 Wire, 1 CT Terminal Connections...
  • Page 11 SMART 7KT0307 Manual Configuration There are two dedicated keys “F1” and “F2”. Keys have multiple assignments. Function assignments and key labelling change according to the context of operator input. For reading serial number Touch F1 key for 3 sec. to display 8-digit serial number only for 5 sec. The serial number will be displayed in 2 pages - 4 digits each. Eg.: For serial number 11220002, the display will be: Page 1: 1122 Page 2: 0002 Automatic / manual mode Auto / Manual mode can be set in configuration setting. By default, unit operates in automatic mode. In automatic mode online pages scroll automatically at the rate of 5 seconds per page. In automatic mode when any key is pressed, unit temporarily switches to manual mode and the appropriate page is displayed. If any key is not pressed for 5 sec, unit resumes automatic mode. In manual mode, unit shows the last set page after power on. Password to start configuration When the meter is set to configuration mode by touching keys F1 + F2, the password page will display which shows the password 000.
  • Page 12 SMART 7KT0307 Manual Parameterization with function keys Factory Network selection and wiring input Sequence Function Range or Selection Setting Network selection Wiring Input Password 000 to 998 Configuration mode Change password No / Yes 3P4W 3P4W New password 000 to 998 3P3W 3P3W Network selection 3P4W / 3P3W / 3P4W 1P2W-R 1P2W-R...
  • Page 13 SMART 7KT0307 Manual Reading of parameters Touch Online Page Touch Online Page Touch Online Page Description Description Description 3P4W 3P3W 1P2W-R After – Displays R phase line- After – Displays R-Y phase After – Displays R phase Power ON neutral voltage Power ON line-line voltage Power ON line-neutral voltage Touch F2 Displays Y phase line- Touch F2 Displays Y-B phase...
  • Page 14 SMART 7KT0307 Manual Reading of parameters (Continued) Touch Online Page Touch Online Page Touch Online Page Description Description Description 3P4W 3P3W 1P2W-R Touch F1 – Displays R phase Touch F1 – Displays max Touch F1 – Displays R phase Key 5th active power Key 11th demand of total...
  • Page 15 SMART 7KT0307 Manual Reading of parameters (Continued) Touch Online Page Touch Online Page Touch Online Page Description Description Description 3P4W 3P3W 1P2W-R Touch F1 – Displays import Key 10th reactive energy of 1st time phase Touch F2 Displays import 1st time reactive energy of 2nd phase Touch F2 Displays import 2nd time...
  • Page 16 SMART 7KT0307 Manual Communication Protocol and interface Connection diagram for communication Protocol: Modbus RTU Interface: Integrated RS485 interface Communication parameters Communication address 1 to 255 Transmission mode Half duplex Data types Float and Integer Transmission distance 500m maximum Transmission Speed 300, 600, 1200, 2400, 4800, 9600, 19200 (in bps) Parity None, Odd, Even Stop bits 1 or 2 Response Time 100ms Max & Independent, at Baud rate...
  • Page 17 SMART 7KT0307 Manual Modbus register addresses list (Continued) Address Hex Address Parameter Address Hex Address Parameter 30084 0x54 Import kWh1 30112 0x70 Total Import kVArh 30086 0x56 Import kWh2 30114 0x72 Total Export kVArh 30088 0x58 Import kWh3 30116 0x74 kVAh1 30090 0x5A Export kWh1 30118 0x76 kVAh2...
  • Page 18: Maintenance

    Maintenance Guidelines • The equipment should be cleaned regularly to avoid blockage of ventilating parts. • Clean the equipment with a clean dry or damp cloth. Do not use any cleaning agent other than water. Disposal and recycling Dispose of or recycle the module in accordance with the applicable laws and regulations in your country.
  • Page 19 These instructions do not purport to cover all details or variations in Siemens. Any statements contained herein do not create new warranties equipment, or to provide for every possible contingency in connection or modify the existing warranty. with installation, operation, or maintenance. Should additional Trademarks - Unless otherwise noted, all names identified by ® are information be desired, please contact the local Siemens sales office. The registered trademarks of Siemens AG or Siemens Industry, Inc. The contents of this instruction manual shall not become part of or modify remaining trademarks in this publication may be trademarks whose use any prior or existing agreement, commitment, or relationship. The...