AEG PROTECT C Series User Manual page 97

Table of Contents

Advertisement

Available languages

Available languages

Description
Adjustable parameters
Ambient
[enabled], [disabled]
temperature
If enabled, UPS alarm when ambient
warning
temperature >40 °C
REPO
[normally open], [normally closed]
operation
Normally open means UPS makes a
shutdown by a closing input state.
Normally closed means UPS makes a
shutdown by an opening input state.
Setting only available in UPS stand-
by mode.
Reset
[no], [yes]
Cumulative
If "no", no action.
Consumption
If "yes", the Cumulative Consumption
kWh
kWh value is cleared and the date
and time stamp for this statistic is set
to the current date and time.
Battery
5h, 6h, ...14h, 15h, 16h, ...999h,
limit time
disabled
Default "14h" means when work on
battery mode for more than 14 hours,
UPS will make bat low alarm and then
shutdown itself 30 minutes later even
battery voltage still above the
shutdown value.
Disabled means "No time limitation"
for battery mode.
Auto reboot
[enabled], [disabled]
Enabled means UPS will auto restart
to normal mode while utility recover
after the UPS has been shutdown for
battery low.
Presetting
enabled
normally closed
no
14h
enabled
EN
EN