Note
In order to minimize noise emission, shielded cables should be used.
Note
The maximum cable length for a shielded cable – connected at both ends – to the
temperature sensor and to the analog inputs is 30 m.
4.3.4

X521 three-phase line supply voltage sensing up to 100 V (phase-to-phase)

Table 4- 4
Terminal block X521
Terminal
1
2
3
Max. connectable cross-section: 1.5 mm²
NOTICE
Only one of the two terminals X521 and X522 may be used. Nothing may be connected to
the unused terminal.
NOTICE
The phases must be connected to the VSM10 with the same sequence as that of the Power
Module.
Voltage Sensing Module 10 (VSM10)
Operating Instructions, 03/2012, A5E02142235A
Designation
Phase voltage U
Phase voltage V
Phase voltage W
4.3 Interface description
Technical data
Connection for voltage sensing via a
transformer with protective separation
Electrical installation
17