Page 3
Introduction General scope of services Tests Converter SINAMICS G150 Type 6SL37102G Reference Manual This documentation pertains to LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Edition 02/2019...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Note If the scope of testing and inspection cannot fulfill all customer requirements, please consult your Siemens sales advisor at head office. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
5. Preparation of test documentation for the customer. The test documentation is created before or after the customer leaves depending on the scope of testing and the time schedule. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Page 10
PD LD scope of supply. This also applies to components ordered from other Siemens' Groups. The technical data for these components is required at the latest eight weeks before the start of the acceptance test, e.g.: ●...
General scope of services 2.1 Routine test Routine test During production, the drive is subject to an internal routine test. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Siemens directives within the scope of quality assurance. The function tests are performed and documented in the Siemens test field by internal test field personnel. For the function test, the drive is in the test mode with restricted monitoring functions.
The successful test is confirmed in a 3.1 certificate – or in the case that the customer has ordered the acceptance test, in a 3.2 certificate. See also Insulation test (Page 29) SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Tests The tests that have been expressly ordered for the drive with serial number 12345670001001 are listed in the following. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
– Fittings and rubber seals in the doors and between the cabinet units – Cable entries – Openings for water pipes, if available – Additional components, if available SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Result The inspection is passed if the cable installation does not exhibit any deficiencies and matches the information in the circuit diagram. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
The drive dimensions are measured. The basis for the visual inspection is the order-specific dimension drawing. Test procedure 1. The external dimensions, length, width and height of the drive are measured. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
A check is made as to whether the mechanical housing design of the ordered marine version complies with what is described in the catalog. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Page 20
– Door bracing – Frame bracing – Handrail Result The check is passed if the components required for the marine version are available. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
In automatic configuration, the installed DriveCLiQ components are detected and displayed on the test station computer. Actual and reference state of the DriveCLiQ topology are compared. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
2. The lighting is checked. Result The test is passed if the correct voltage is available at the socket outlets and the lighting functions. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
The tests are performed according to IEC 60146-1-1 and IEC 60204-11. The safety shutdown of the power section is tested according to the category that was ordered. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Fundamentals The drive shuts down if the DC link voltage fails. DC link voltage failure is simulated by switching off the supply. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Page 25
Result The test is passed if the drive is shut down and the appropriate message is displayed on the test station computer. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
The drive synchronizes itself with the motor, and controls it to the speed that was last set. Result The test is passed if the speed last set is returned to after the drive has recovered. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Result The test is passed if the appropriate messages are displayed on the test station computer, and the drive is shut down. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
3. The air flow direction is checked at the ventilation grilles. Result The test is passed if the air flows from the doors up to the roof section. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Result The test is passed if the test instrument is not switched off (tripped) during the test as a result of flashover. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Result The test is passed if the insulation resistances lie within the tolerance specified by the standard. SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Rev.201902141443 LV Umrichter...
Page 34
8888888888 000088 01 EN 01 Further Information www.siemens.com/drives Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY *888888888800008801EN01* 888888888800008801EN01...
Page 35
Process Industries and Drives Department PD LD P MF-NMA EN Siemens AG, PD LD P MF-NMA EN, Postfach 47 43, 90025 Nürnberg Tel. +49 (911) 433-6422 +49 (911) 433-6921 Email motoren.doku.aud@internal.siemens.co Our ref. 8888888888000088 Date 14.02.2019 Documentation for 6SL37102G Your order no. - 000010...
Page 37
E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Tests carried out on drives Spine label for binder 162 mm (120 g/m2) SINAMICS G150 6SL37102G LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Tests carried out on drives...