Tests
3.2 Function test
Test procedure
1. The auxiliary voltage is present.
2. The DriveCLiQ connector is removed at any DriveCLiQ component.
Result
The test is passed if the appropriate message is displayed on the test station computer.
3.2.4

Anti-condensation heating

Fundamentals
A check is made as to whether the anti-condensation heating heats up after switching on. This
prevents the formation of condensation in the drive when it is not operational.
Test procedure
1. The temperature of the anti-condensation heating is measured using an infrared
2. The auxiliary voltage for the anti-condensation heating is switched on.
3. The temperature is measured again.
Result
The test is passed if the anti-condensation heating elements heat up after they have been
switched on.
3.2.5

Socket outlets and lighting

Fundamentals
Socket outlets and lighting are checked.
Test procedure
1. The voltage at the socket outlets is measured.
2. The lighting is checked.
Result
The test is passed if the correct voltage is available at the socket outlets and the lighting
functions.
22
A message is displayed on the test station computer.
thermometer.
The anti-condensation heating elements heat up.