2.4

Information on refrigerant

This device contains fluorinated greenhouse gases as refrigerant. The
unit is hermetically sealed. The following information on the refrigerant
complies with the requirements of EU Regulation No. 517/2014 on
fluorinated greenhouse gases.
Product type
Rated cooling
output
[kW]
CL5000M 41/2 E
3.52
CL5000M 53/2 E
5.28
CL5000M 62/3 E
7.03
CL5000M 79/3 E
8.79
CL5000M 82/4 E
10.55
CL5000M 105/4 E
10.55
CL5000M 125/5 E
12.02
1) Total pipe length L in metres (if L > 5 m simple path from outdoor unit to indoor unit).
Table 29 F-Gas
3

Operation and maintenance

CAUTION
Danger due to electric shock or moving parts
▶ Disconnect the power supply before carrying out any maintenance
work.
▶ Have any maintenance steps that are not listed here carried out by an
approved installer.
You can find information on operating the indoor units in the
corresponding operating instructions.
3.1

Operating mode conflict

When using multi-split air conditioners, all operating modes are
possible, but with the following special features:
If you operate more than one indoor unit, indoor units may go into
standby due to an operating mode conflict. An operating mode conflict
occurs when at least one indoor unit is in heating mode and at least one
indoor unit is in another operation mode at the same time (e.g. cooling
mode). Heating mode always has priority. All indoor units that are not in
heating mode go into standby due to the operating mode conflict.
Indoor units with operation mode conflict show "−−" in the display or the
ON indicator flashes and the timer indicator is on. See technical
documentation of the indoor unit for more information.
Avoid the operating mode conflict:
• No indoor unit is in heating mode.
• All indoor units are in heating mode and/or off.
Climate 5000 M – 6721849820 (2022/11)
Rated heating
Refrigerant
output
Type
[kW]
3.81
R32
5.57
R32
7.62
R32
9.38
R32
11.72
R32
11.72
R32
13.48
R32
Notice for the user: If your installer adds refrigerant, he enters the added
fill volume and the total amount of the refrigerant in the following table.
Global
CO
Initial
2
warming
equivalent
charge
potential
of initial
volume
(GWP)
charge
[kg Co
2
equ.]
675
0.49
675
0.78
675
1.01
675
1.35
675
1.62
675
1.62
675
1.89
Operation and maintenance
Additional fill
Total charge
volume for
volume during
pipe length
commissioning
1)
[kg]
L
[g/m]
0.72
12
1.15
12
1.5
12
2.0
24
2.4
24
2.4
24
2.8
24