Lan/Ethernet Connection With L240/Ip - ABB L240 Product Manual

Security technology software win-pc for intrusion alarm panel
Table of Contents

Advertisement

3.3
LAN/Ethernet connection
with L240/IP
6
Software WIN-PC for Intrusion Alarm Panel L240
• In submenu "04=SiteID" a SiteID must be entered for the panel. This
SiteID in the panel must be identical with the SiteID in the database of
the PC Software (WIN-PC). When communication is established, both
SiteIDs are compared and communication will only be possible if they
are identical.
SiteID
1234
Entry of the SiteID
Acknowledge the SiteID with the "Return" button, then exit the function
"04=SiteID" with the "ESC" button.
• Exit programming by repeated actuation of the "ESC" button until
"=Confirm Logoff" is displayed. After pressing the "Return" button,
the base display appears.
The IP Interface is installed in the same enclosure as module L208/V24.
Two connections are also available here:
On the circuit board, the 4-core XIB-Bus from the Intrusion Alarm Panel
should be connected to the conductors +/-/A/B.
A network socket can be found on the right side.
On the additional connection "Keypad 0", a L840/PT with address 0 can
be connected and used to program the Intrusion Alarm Panel or to enable
the connected interface module in the Hardware menu of the panel.
8
7
6
5
Keypad 0
XIB Data
XIB from
panel
The plug-in jumpers LK1 and LK2 can be used for bypassing the panel
tamper contacts to suppress the tampering alarm during commissioning
(otherwise tamper alarm).
Jumpers LK1 and LK2 must be removed again after commissioning.
Connection
• The network connection is carried out via an Ethernet RJ45 interface
for LAN networks. A crossover cable is required for connection to the
network card of a PC. A normal patch cable is required to connect
via a router or switch.
• On the IP Module L240/IP, set DIP switch 1 to "ON", DIP switches 2-8
must be set to "OFF".
• Connect IP module (terminal CN1 XIB) during operation to the XIB
security bus. Connection to the external (terminal CN13) or internal
(terminal CN11) XIB security bus of the panel is possible.
ON
4
3
2 1
Panel
tamper
Tamper
contact
jumper
Collision
Ethernet
10 BaseT
Data

Advertisement

Table of Contents
loading

Table of Contents