15 LAN Interface L240/IP

15.1 General

Serial Interface L208/V.24
Connection
Baud-9600
 In submenu "02=Operations" the "Auto" parameter should be selected.
Operations
Enable-Auto
 In submenu "03=Auth Code" an enable code can be entered. As enable
occurs without code, this function is not relevant and no entries must be
made.
Auth Code
Auth Code-000
 In submenu "04=SiteID" a 4-digit customer number must be entered for
the panel. This customer number in the panel must be identical with the
customer number in the database of the PC Software (WIN-PC). When
communication is established, both customer numbers are compared and
communication will only be possible if they are identical.
SiteID
1234
The connection of the L240 to the PC is implemented either via a serial
interface with the Interface Module L208/V.24 or via a LAN network with the
IP Interface L240/IP.
The IP Interface is installed in the same enclosure as module L208/V24.
Two connections are also available here:
On the circuit board, the 4-core XIB-Bus from the Intrusion Alarm Panel
should be connected to the conductors +/-/A/B.
A network socket can be found on the right side.
On the additional connection "Keypad 0", a L240/PT with address 0 can be
connected and can be used to program the Intrusion Alarm Panel or to
enable the connected interface module in the Hardware menu of the panel.
Note: Only one Interface Module L208/V.24 or L240/IP can be operated on
the panel at one time.
1
Press button
for baud rate of 9600 Baud
2
Press button
to set enable to "Auto"
Entry of the customer number
104