15.2 Circuit diagram

15.3 Commissioning

15.4 Setting the IP address of
the PC
LAN Interface L240/IP
Keypad 0
XIB data
XIB from panel
The plug-in jumper LK1 and LK2 can be used for bypassing the panel
tamper contacts to suppress the tampering alarm during commissioning
(otherwise tamper alarm). Jumpers LK1 and LK2 must be removed again
after commissioning.
The module L240/IP is automatically logged on in the factory setting of the
L240. Log on and off is not necessary. In the logon menu of the interface the
L240/IP is displayed as a L204/V.24, see chapter 14.3 "Login L204/V.24".
Connection
 The network connection is carried out via an Ethernet RJ45 interface for
LAN networks. A crossover cable is required for connection to the
network card of a PC. A normal patch cable is required to connect via a
router or switch.
 On the IP Module L240/IP set DIP switch 1 to "ON", DIP switches 2-8
must be set to "OFF".
 Connect IP module (terminal CN1 XIB) during operation to the XIB
security bus. Connection to the external (terminal CN13) or internal
(terminal CN11) XIB security bus of the panel is possible.
 As soon as the IP module is supplied with voltage, the Intrusion Alarm
Panel will be informed of the set PC function.
 Green LED 1 indicates correct communication with the Intrusion Alarm
Panel by fast flashing.
 The three yellow LEDs indicate the function of the LAN interface.
The "Ethernet" LED lights when connected to a network. The "Data" LED
flashes during function data transmission, and the "Collision" LED lights
up in the event of a fault.
 After commissioning, remove jumpers LK1 and LK2 and close the
enclosure cover.
The Interface Module L240/IP requires a fixed IP address setting for
operation. The network section of the address (defined by the subnet mask)
must comply over the entire network. The device section of the address
(generally the last number block) is used for addressing the individual
devices.
ON
8
7
6
5
4
3
2 1
Panel tamper
Panel
tamper
links
Collision
Ethernet
Data
10 BaseT
105