Description Of The Inputs And Outputs; Addressing - ABB L240 Series Installation, Commissioning & Operation

Security technology knx-intrusion alarm system
Hide thumbs Also See for L240 Series:
Table of Contents

Advertisement

Cct
2 sensor
connected
XIB
Note:
Cable entry for both circuits is on the
same side. The circuit input is on the
left, the termination resistor on the
right.

10.3 Description of the inputs and outputs

Terminal block
Function
CN2
Output for the supply voltage of detectors
+
XIB security bus
-
A
B
CN1 and CN3
Detector circuits, freely programmable
Red LED
Display tamper contact/circuit fault
LED green
Operation

10.4 Addressing

L240/MG2
On both left terminals the circuit input (evaluation) is connected, both the
middle terminals are used for connection terminals and the termination
resistor is integrated into both of the right terminals.
The number of the circuit is on the left beside the DIP switch followed by the
number of the circuit on the right beside the XIB terminal block.
Example:
The detector circuit module is registered on the panel. The panel occupies
circuits 1-10; on the circuit module circuit 11 is located on the right beside
the XIB terminal block, and circuit 12 on the left beside the DIP switch.
Cct
1 sensor
connected
C on n ec tio n o f 2 se ns o rs:
Bo th m idd le con tacts are sim ply us ed as
intercon ne ction term ina ls.
The circuit module is addressed via a DIP switch.
A maximum of up to 24 circuit modules L240/MG2 can be managed by the
panel. The Detector Circuit Modules L240/MG2 and L840/MG4 have a
common addressing range on the XIB bus from 1 to 24. Numbering of the
circuit is undertaken consecutively to the addresses of the circuit module.
Before teaching-in bus motion detectors, all Detector Circuit Modules
L240/MG2 and L840/MG4 must be logged on!
C o nn ectio n o f a sens or:
B oth m idd le c o ntac ts rem a in
free .
Description
Protected by fuse F1 with 100 mA
Supply voltage + 12 V
0 V
Data line A
Data line B
Every detector group must be terminated with the
integrated 2.7k Ohm resistor in the normal state
ON: Tamper alarm (tamper contact is triggered) or at least
one detector group faulty
OFF: Tamper contact not triggered or monitoring
deactivated:
ON: Module not logged on
Flashes (1 Hz): Module logged on
72