12.6 Commissioning

L240/BS
The following procedure must be observed when putting the Intrusion Alarm
Panel L240 and the Evaluation Module L240/BS into operation. The
commissioning instructions in the product manual of the Intrusion Alarm
Panel, strike plate and door cylinder must be observed.
Important: During all installation and commissioning work, such as
Modifications on the DIP switch settings
Connection or disconnection of the Evaluation Module L240/BS with the
XIB security bus,
the Intrusion Alarm Panel must be powered off (mains and battery supply
disconnected). The installation and commissioning may only be carried out
by electrical specialists!
Should evaluation modules be logged off in the programming level (Menu
"Hardware"), they should be subsequently disconnected from the XIB
security bus.
1. Intrusion Alarm Panel L240 commissioning:
The power supply to the Intrusion Alarm Panel must be switched off, and no
sensors or detectors should be initially connected, rather
The zones (inputs 1 to 6 and 8 to 10) with the 2.7 kOhm end of line
resistor must be connected directly to the terminals
The lock detector circuit (input 7) must be bypassed without a resistor
The outputs for both sirens and strobe lights are to be fitted with the 1
kOhm end of line resistor directly on the terminals
The tamper input for the cover tamper contact, the input Comm fault and
Comm alarm must be connected with a jumper to 0V
At least one LCD Keypad L240/PT with address 1 must be connected to the
external bus (XIB). A total of maximum 8 keypads can be connected. Using
this keypad, it is possible to program and manage the chipkey and keypad
code in addition to operating the Intrusion Alarm Panel.
No detector circuit for setting the Intrusion Alarm Panels may be used (e.g.
circuit 10 of the L240). This detector circuit only needs to be terminated with
a resistor (2.7 kOhm) or can be reprogrammed , e.g. as an intrusion detector
group.
2. Mounting the door cylinder/strike plate/wall reader:
The wall reader should be mounted. Refer to the corresponding product
manual or technical data sheet for this purpose.
Should there be a communication fault (e.g. during set-up or
commissioning) between an Evaluation Module L240/BS and a strike
plate or door cylinder, the Intrusion Alarm Panel cannot be set/unset or
the door cannot be opened.