Menu 05 "Alarm Times - ABB L240 Series Installation, Commissioning & Operation

Security technology knx-intrusion alarm system
Hide thumbs Also See for L240 Series:
Table of Contents

Advertisement

Configuration and Programming by the Engineer
8.1.5

Menu 05 "Alarm Times"

Engineer-PIN
8 = Edit
01 = System Size
02 = Area Opts
03 = Circuits
04 = Relay
05 = Alarm Times
06 = Keypads
07 = Concs *
08 = User Auth
09 = Text
10 = L240/B/BS*
11 = XS/1.1 KNX *
13 = 2-Conc Tamper *
15 = Defaults
16 = XIB-Detectors
Menu item "05=Alarm Times": The response of the panel to different
alarms (e.g. external or personal attack alarm) can be programmed
accordingly.
After selection of the menu, the following request appears with factory
default settings:
Alarm Times
Time-180
Setting of the alarm time (response time of both sirens, the output "Intrusion"
and "Internal alarm").
Alarm Times
IntAlmStrobe-Off
With "On" for an internal alarm, the strobe and the permanent alarm relay
are also controlled (VdS).
Alarm Times
ExtAfterInt-Off
At "On" with internal setting and an internal alarm, an external alarm is
triggered after the alarm time has elapsed (sirens and strobes) (VdS).
Alarm Times
Silent Alarm-Off
With "On" the panel only generates silent alarms (output "Intrusion") and the
local alerting (sirens and strobes) is not actuated.
Exception: If a dialling device (comm) cannot send the silent alarm, a
negative acknowledgement is displayed on the input "Comm alarm" and
local alerting is actuated.
Alarm Times
EntryFullAlm-Off
With delayed setting/unsetting, after the entry time of the set/unset circuit
has timed out, an external alarm is triggered.
Alarm Times
TamIntAlm-On
At "On" with a tampering alarm in unset, an additional internal alarm is
triggered.
(Limit 1-180)
Enter: 0=OFF; 1=ON
Enter: 0=OFF; 1=ON
Enter: 0=OFF; 1=ON
Enter: 0=OFF; 1=ON
Enter: 0=OFF; 1=ON
59