ABB Relion 670 Series Product Manual

ABB Relion 670 Series Product Manual

Busbar protection customized
Hide thumbs Also See for Relion 670 Series:

Advertisement

Quick Links

®
Relion
670 series
Busbar protection REB670
Customized
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670 series Busbar protection REB670 Customized Product Guide...
  • Page 2: Table Of Contents

    11. Logic................20 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Application

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Issued: February 2015 Revision: D 1. Application The numerical, low-impedance differential protection function REB670 is designed for the selective, reliable and fast is designed for fast and selective protection for faults within differential protection of busbars, T-connections and meshed protected zone.
  • Page 4 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Sensitive differential protection Operate region Differential protection operation characteristic Diff Oper Level Sens Iin Block Sensitive Oper Level s=0.53 [Primary Amps] en06000142.vsd IEC06000142 V1 EN Figure 1. REB670 operating characteristic Integrated overall check zone feature, independent from any faults within the blind spot or the end zone between bay CT disconnector position, is available.
  • Page 5 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 The wide application flexibility makes this product an Application examples of REB670 excellent choice for both new installations and the Examples of typical station layouts, which can be protected refurbishment of existing installations. with REB670 are given below: Optional apparatus control for up to 30 objects can provide a facility to draw simplified single line diagram (SLD) of the...
  • Page 6 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 IEC11000239-1-en.vsd IEC11000239 V1 EN Figure 5. Example of double bus-single breaker station QB20 xx06000015.vsd IEC06000015 V1 EN Figure 6. Example of double bus-single breaker station with transfer bus QB1 QB2 QB1 QB2...
  • Page 7 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 IEC11000240-1-en.vsd IEC11000240 V1 EN Figure 8. Example of one-and-a-half breaker station xx06000018.vsd IEC06000018 V1 EN Figure 9. Example of double bus-double breaker station QB12 QB11 QB41 QB21 QB42 QB22 QB31 QB32 xx06000019.vsd IEC06000019 V1 EN Figure 10.
  • Page 8 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Note that customized REB670 is delivered without any configuration. Thus the complete IED engineering shall be done by the customer or its system integrator. In order to secure proper operation of the busbar protection it is strictly recommended to always start engineering work from the PCM600 project for the pre-configured REB670 which is the closest to the actual application.
  • Page 9: Available Functions

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 2. Available functions Main protection functions = number of basic instances = option quantities IEC 61850 ANSI Function description Busbar REB670 Differential protection BUTPTRC, Busbar differential protection, 2 zones, three phase/up to 8 bays BCZTPDIF, BZNTPDIF, BZITGGIO...
  • Page 10: Current Protection

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Busbar REB670 Current protection OC4PTOC 51_67 Four step phase overcurrent protection PH4SPTOC Four step single phase overcurrent protection 0-24 TRPTTR Thermal overload protection, two time constant CCRBRF 50BF Breaker failure protection...
  • Page 11: Secondary System Supervision

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Busbar REB670 Control SMBRREC Autorecloser APC30 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking QCBAY Apparatus control 1+5/APC30 LOCREM Handling of LRswitch positions...
  • Page 12: Metering

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 IEC 61850 ANSI Function description Busbar REB670 Metering PCGGIO Pulse-counter logic ETPMMTR Function for energy calculation and demand handling Designed to communicate IEC 61850 ANSI Function description Busbar REB670 Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication protocol...
  • Page 13: Basic Ied Functions

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup Parameter setting groups Test Test mode functionality ChangeLock...
  • Page 14 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 saturated for at least two milliseconds during each power restraint quantity. If required, the check zone operation can system cycle. It is also possible to add external tripping be activated externally by a binary signal. criteria by binary signal.
  • Page 15 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 these disconnectors then actually determine which CT input Note that the first scheme only requires fast breaking normally (that is, bay) is connected to which differential protection closed auxiliary contact (that is, b contact) for proper zone.
  • Page 16 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 • Permanently connect this bay current to zone A (that is, The third option ensures that the feeder, which is out of service, is not connected to any of the two zones during zone •...
  • Page 17 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 5. Current protection value, the protection initiates a trip of the protected transformer/generator. Four step phase overcurrent protection OC4PTOC The four step phase overcurrent protection function Breaker failure protection CCRBRF OC4PTOC has an inverse or definite time delay independent Breaker failure protection (CCRBRF) ensures fast back-up for step 1 and 4 separately.
  • Page 18 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Capacitor bank protection (CBPGAPC) Loss of voltage check LOVPTUV Shunt Capacitor Banks (SCB) are used in a power system to Loss of voltage check (LOVPTUV) is suitable for use in provide reactive power compensation and power factor networks with an automatic system restoration function.
  • Page 19 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 neutral voltages to be connected. For information about how used for delayed busbar restoration. One Autorecloser to connect analog inputs, refer to Application manual/IED (SMBRREC) per zone can be made available. application/Analog inputs/Setting guidelines.
  • Page 20 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 • LOOPDELAY function block used to delay the output signal Selector mini switch VSGGIO one execution cycle. The Selector mini switch VSGGIO function block is a multipurpose function used for a variety of applications, as a •...
  • Page 21 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 The function requires that the IED is equipped with the mA in the short perspective to get information via the local HMI in input module. a straightforward way. Event counter CNTGGIO There are three LEDs on the local HMI (green, yellow and Event counter (CNTGGIO) has six counters which are used for red), which will display status information about the IED and...
  • Page 22: Human Machine Interface

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 The function is characterized by great flexibility and is not Function for energy calculation and demand handling dependent on the operation of protection functions. It can ETPMMTR record disturbances not detected by protection functions. Up Outputs from the Measurements (CVMMXN) function can be to ten seconds of data before the trigger instant can be saved used to calculate energy consumption.
  • Page 23 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 IEC06000191 V1 EN IEC06000143 V1 EN Figure 12. Bay to zone connection example Figure 11. Example of medium graphic HMI 1 User settable bay name 2 Internally used bay FB 3 Connections to internal zones...
  • Page 24: Station Communication

    ABB IED's and the new IED 670. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation Monitoring Systems SMS.
  • Page 25: Remote Communication

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 17. Remote communication Binary input/output module IOM The binary input/output module is used when only a few input Analog and binary signal transfer to remote end and output channels are needed. The ten standard output Three analog and eight binary signals can be exchanged channels are used for trip output or any signaling purpose.
  • Page 26 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 IRIG-B Time synchronizing module by the measuring transformers. The module has twelve inputs The IRIG-B time synchronizing module is used for accurate in different combinations of currents and voltage inputs. time synchronizing of the IED from a station clock. Alternative connectors of Ring lug or Compression type can Electrical (BNC) and optical connection (ST) for 0XX and 12X be ordered.
  • Page 27: Connection Diagrams

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 19. Connection diagrams Table 2. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132 X301:A, B, C, D LDCM, IRIG-B or X302...
  • Page 28 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 1MRK002801-AC-10-670-1.2-PG V1 EN Figure 15. Transformer input module (TRM) ■ Indicates high polarity CT/VT-input designation according to figure AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 12I, 1A 12I, 5A 9I+3U, 1A 110-220V...
  • Page 29 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 1MRK002801-AC-15-670-1.2-PG V1 EN Figure 17. mA input module (MIM) 1MRK002801-AC-11-670-1.2-PG V1 EN Figure 16. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
  • Page 30 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 1MRK002801-AC-7-670-1.2-PG V1 EN Figure 19. Power supply module (PSM) 1MRK002801-AC-12-670-1.2-PG V1 EN Figure 20. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 31 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 1MRK002801-AC-13-670-1.2-PG V1 EN Figure 21. Static output module (SOM) 1MRK002801-AC-14-670-1.2-PG V1 EN Figure 22. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 32: Technical Data

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 20. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its...
  • Page 33 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 5. OEM - Optical ethernet module Quantity Rated value Number of channels 1 or 2 Standard IEEE 802.3u 100BASE-FX Type of fiber 62.5/125 mm multimode fibre Wave length 1300 nm Optical connector Type ST Communication speed...
  • Page 34 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 8. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ± 20% 110/125 V RL ±...
  • Page 35 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 10. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC, DC 250 V DC Test voltage across open contact, 1 min...
  • Page 36 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 11. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2 Max system voltage...
  • Page 37 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 13. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs Test voltage across open contact, 1 min 1000V rms Current carrying capacity: Continuous...
  • Page 38 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 16. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% /% Operative range Full wave rectified Auxiliary voltage dependence, operate...
  • Page 39 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Type tests according to standards Table 18. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Ring wave immunity test, 100 kHz...
  • Page 40 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 20. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C IEC 60068-2-1 Dry heat test Test Bd for 16 h at +70°C IEC 60068-2-2...
  • Page 41 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Differential protection Table 23. Busbar differential protection Function Range or value Accuracy Operating characteristic S=0.53 fixed ± 2.0% of I for I < I ± 2.0% of I for I > I Reset ratio >...
  • Page 42 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Current protection Table 24. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy lBase Operate current (5-2500)% of ± 1.0% of I at I ≤ I ± 1.0% of I at I > I lBase Reset ratio >...
  • Page 43 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 26. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ± 1.0% of I Operate time: = load current before overload IEC 60255–8, ±5% + 200 ms occurs æ...
  • Page 44 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 29. Directional underpower protection GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ± 1.0% of S at S < S ± 1.0% of S at S > S At low setting: (0.5-2.0)% of SBase...
  • Page 45 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 31. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (0-900)% of lBase ± 1.0% of I at I < I ± 1.0% of I at I > I Reset ratio, overcurrent >95% Operate time, start...
  • Page 46 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Voltage protection Table 32. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1–100)% of ± 0.5% of U UBase Absolute hysteresis (0–100)% of ±...
  • Page 47 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 34. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 and step 2 (1-200)% of UBase ± 0.5% of U at U < U ±...
  • Page 48 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Frequency protection Table 37. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz Operate time, start function 100 ms typically Reset time, start function 100 ms typically Operate time, definite time function (0.000-60.000)s...
  • Page 49 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Multipurpose protection Table 40. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2- phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph Base current (1 - 99999) A...
  • Page 50 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 40. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Relay characteristic angle (-180 to +180) degrees ± 2.0 degrees Relay operate angle (1 to 90) degrees ±...
  • Page 51 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Secondary system supervision Table 41. Fuse failure supervision SDDRFUF Function Range or value Accuracy Operate voltage, zero sequence (1-100)% of UBase ± 1.0% of U Operate current, zero sequence (1–100)% of IBase ±...
  • Page 52 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Control Table 42. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms shot 1 - t1 2Ph shot 1 - t1 3PhHS shot 1 - t1 3PhDld...
  • Page 53 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Logic Table 43. Configurable logic blocks Logic block Quantity with update rate Range or value Accuracy fast medium normal LogicAND LogicOR LogicXOR LogicInverter LogicSRMemory LogicRSMemory LogicGate LogicTimer (0.000–90000.000) s ± 0.5% ± 10 ms LogicPulseTimer (0.000–90000.000) s ±...
  • Page 54 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Monitoring Table 44. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×U ± 0.5% of U at U£U ± 0.5% of U at U > U Connected current (0.2-4.0) ×...
  • Page 55 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 48. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.2% of I at I ≤ 0.5 × I Three phase settings ±...
  • Page 56 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 52. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms See table...
  • Page 57 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 56. Trip value recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of disturbance reports Table 57. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports Maximum total recording time (3.4 s recording time and maximum number...
  • Page 58 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Metering Table 58. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 59. Energy metering ETPMMTR Function Range or value Accuracy...
  • Page 59 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Station communication Table 60. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 60 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 65. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fibre: type ST Plastic fibre: type HFBR snap-in Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *) Plastic fibre: 7 dB (80ft/25 m typically *) Fibre diameter Glass fibre: 62.5/125 mm...
  • Page 61 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Remote communication Table 68. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fibre Graded-index Singlemode 9/125 µm Singlemode 9/125 µm multimode 62.5/125 µm or...
  • Page 62 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Hardware Table 69. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 70. Water and dust protection level according to IEC 60529 Front IP40 (IP54 with sealing strip) Sides, top and bottom...
  • Page 63 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Basic IED functions Table 74. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 75. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 64 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 78. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp – high level 3 x low level, max 9 Vpp Supported formats IRIG-B 00x, IRIG-B 12x...
  • Page 65 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Inverse characteristic Table 79. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø EQUATION1249-SMALL V1 EN Reset characteristic: ×...
  • Page 66 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 80. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø EQUATION1251-SMALL V1 EN I = I measured Time delay to reset, IEC inverse time...
  • Page 67 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 82. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö > ç ÷ è...
  • Page 68 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 83. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö < - ç ÷...
  • Page 69 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Table 84. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 5% +40 ms 0.01 æ ö > ç ÷...
  • Page 70: Ordering

    Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 21. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Please refer to the available functions table for included application functions.
  • Page 71 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Current protection Rule: Only one of OC4PTOC and PH4SPTOC can be ordered Four step phase overcurrent protection (OC4PTOC) Qty: 1MRK 002 906-BD Four step single phase overcurrent protection (PH4SPTOC) Qty: 1MRK 002 907-BB 10 11 12 14 15 16 17 18 19 20 21...
  • Page 72 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Frequency protection Underfrequency protection (SAPTUF) Qty: 1MRK 002 908-NC Overfrequency protection (SAPTOF) Qty: 1MRK 002 908-RC Rate-of-change frequency protection (SAPFRC) Qty: 1MRK 002 908-SB Multipurpose protection General current and voltage protection (CVGAPC) Qty: 1MRK 002 902-AB Secondary system supervision...
  • Page 73 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Additional local HMI user dialogue language Rule: Maximum one alternative HMI language, German 1MRK 002 920-AB HMI language, Russian 1MRK 002 920-BB HMI language, French 1MRK 002 920-DB HMI language, Spanish 1MRK 002 920-DB HMI language, Polish 1MRK 002 920-GB...
  • Page 74 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Analog system Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals 12I, 1A, 50/60 Hz Qty: 1MRK 002 247-CG Transformer input module, compression terminals 12I, 5A, 50/60 Hz Qty: 1MRK 002 247-CH...
  • Page 75 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Maximum quantity of I/O modules Case sizes BOM/ Maximum in case 1/1 x 19”, two (2) TRM 11 (max 4 BOM+SOM 1MRK 000 151-ND +MIM) Maximum quantity of I/O modules, with ring lug terminals, module limits see above Case sizes Maximum in case Possible locations for I/O modules...
  • Page 76 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Binary input/output modules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased. BIM with 30 mA inrush current is still available.
  • Page 77 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 RL 48-60 VDC Qty: 1MRK 000 508-EA 10 11 RL 110-125 VDC Qty: 1MRK 000 508-FA 10 11 RL 220-250 VDC Qty: 1MRK 000 508-GA 10 11 Binary output module 24 output relays (BOM) Qty: 1MRK 000 614-AB 10 11...
  • Page 78 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased. IOM with 30 mA inrush current is still available. Binary input/output module (IOM) 8 inputs, 10 outputs, 2 high-speed outputs RL 24-30 VDC, 30 mA Qty:...
  • Page 79 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Station communication ports Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM. Optical ethernet module, 1 channel glass 1MRK 002 266-AA Optical ethernet module, 2 channel glass 1MRK 002 266-BA Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0 Serial/LON plastic interface...
  • Page 80 670 products is described in 1MRK 512 001-BEN and 1MRK refer to Section "Related documents" for reference to 001024-CA. Please refer to the website: corresponding documents. www.abb.com/substationautomation for detailed information. Test switches type RTXP 24 is ordered separately. Please refer to Section "Related documents" for reference to corresponding documents.
  • Page 81 Busbar protection REB670 1MRK505273-BEN D Customized Product version: 1.2 Configuration and monitoring tools Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA Manuals...
  • Page 82 670 series SPA and signal list 1MRK 500 092-WEN IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN Engineering manual 670 series 1MRK 511 240-UEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 84 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...