Download Print this page
ABB Slimline SPS-48V Quick Start Manual
ABB Slimline SPS-48V Quick Start Manual

ABB Slimline SPS-48V Quick Start Manual

Hide thumbs Also See for Slimline SPS-48V:

Advertisement

Quick Links

QUICK START GUIDE
SPS –48V Slimline Power Shelf
Models: J2007003L004, 014 - alpha suffixes per Slimline Power System
Brochure
No vertical spacing is required, allow a minimum 2 inch clearance at back of shelf for rectifier airflow.
Refer to Slimline Power System Brochure for details and accessories.
Wire cutters and strippers
Cable crimpers
Torque wrench - 0-65 in-lb (0-10 Nm)
1.
Reposition mounting ears as required - 1 screw each. Torque to 25 in-lb (2.8 Nm) - Phillips screwdriver.
2.
Attach shelf to the frame using a minimum of four screws (two on each side) - 12-24 (provided). Torque to 35 in-lb
(4 Nm) - 5/16" socket.
Page 1
© 2021 ABB. All rights reserved.

Advertisement

loading

Summary of Contents for ABB Slimline SPS-48V

  • Page 1 Reposition mounting ears as required - 1 screw each. Torque to 25 in-lb (2.8 Nm) - Phillips screwdriver. Attach shelf to the frame using a minimum of four screws (two on each side) - 12-24 (provided). Torque to 35 in-lb (4 Nm) - 5/16” socket. Page 1 © 2021 ABB. All rights reserved.
  • Page 2 15 A max GMT style fuse Torque to 4 in-lb (0.45 Nm) Torque to 4 in-lb (0.45 Nm) J3 1-Wire Battery Temp Monitor J2 Alarm inputs J1 Alarm outputs J5 LAN Port USB Craft Port Page 2 © 2021 ABB. All rights reserved.
  • Page 3: Step 10 - Initial Start Up

    Verify that all AC, DC and Alarm connections are complete and secure. Turn on AC input breakers. If there are no alarms, make required adjustments to the default settings on the controller for this installation. Verify and edit controller basic configuration parameters per site engineering instructions. Page 3 © 2021 ABB. All rights reserved.
  • Page 4 Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required. 0I5R_D - 5 3C3R - 3 Alarm Color 9C0R_USB - 9 Inputs Color Alarm Re- lays, Input: SPD Fail Page 4 © 2021 ABB. All rights reserved.
  • Page 5 QUICK START GUIDE abbpowerconversion.com • abbpowerconversion.com These documents are available at Document Title 850035894 Galaxy Pulsar Edge Quick Start Guide CC848815341 Pulsar Edge Controller Family Product Manual Slimline Power System Brochure Page 5 © 2021 ABB. All rights reserved.
  • Page 6: Safety Statements

    Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. Page 6 © 2021 ABB. All rights reserved.
  • Page 7 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease with distance. Page 7 © 2021 ABB. All rights reserved.
  • Page 8 With regard to and illustrations contained therein. Any reproduction, disclosure purchase orders, the agreed particulars shall prevail. ABB AG does to third parties or utilization of its contents–in whole or in not accept any responsibility whatsoever for potential errors or parts –...

This manual is also suitable for:

J2007003l004J2007003l014