4-2-5. Network Settings
Network settings vary depending on whether the AE-200/AE-50 is connected to a dedicated LAN or an existing
LAN. See the sections below for how to set the AE-200/AE-50 IP, subnet mask, and gateway addresses in the
[Network Settings] section.
Note: Do not use the LAN2 port.
Note: Although the settings for LAN1 (Network Settings) and LAN2 (Network Settings 2) will appear on the screen, only the
settings for LAN1 is required. However, only when the LAN1 IP address is required to be set to [192.168.2.1], change the
default LAN2 IP address to avoid address overlap.
4-2-5-1. Settings for connecting the AE-200/AE-50 to a dedicated LAN
(1) Enter the AE-200 or AE-50's IP address in the [IP Address] field. If the LAN has been newly set up, allocate
IP addresses to the AE-200 units in a sequential order starting with [192.168.1.1]. For example, the first
AE-200 unit will have an IP address of [192.168.1.1], the second AE-200 unit will have an IP address of
[192.168.1.2] and so on.
Allocate IP addresses to the AE-50 units in a sequential order starting with [192.168.1.211].
Note: The recommended IP address ranges are as follows.
AE-200: Between [192.168.1.1] and [192.168.1.40]
AE-50: Between [192.168.1.211] and [192.168.1.249]
PC: Between [192.168.1.101] and [192.168.1.150]
[IP address setting example]
Note: Some hubs have dedicated ports for connection with another hub.
Connect the AE-200/AE-50 and PC to the normal ports.
(2) Enter [255.255.255.0] in the [Subnet Mask] field (unless otherwise specified).
WT07138X01
100 BASE-TX LAN straight cable
AE-200
AE-50
192.168.1.1
192.168.1.211
Hub
AE-50
192.168.1.212
18
PC
192.168.1.101