Properties
1.1 2AO I ST analog electronic module (6ES7135-4GB01-0AB0)
Crosstalk between the outputs
Operational limit (in the entire temperature range,
with reference to the output range)
Basic error limit (operational limit at 25°C with
reference to output range)
Temperature error (with reference to the output
range)
Linearity error (with reference to the output range) ± 0,02 %
Repeatability
(in steady state at 25°C with reference to output
range)
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
Output range (rated value)
Load resistance
Destruction limit against voltages/currents applied
from outside
Connection of actuators
10
For inductive load
Open circuit voltage
Voltage at the outputs to M
Current
Two-wire connection
Four-wire connection
Suppression of interference, limits of error
Min. -40 dB
± 0,5 %
± 0,3 %
± 0.01 %/K
± 0,05 %
± 0,02 %
Data for selecting the actuator
± 20 mA
4 to 20 mA
Max. 500 Ω
1 mH
18 V
Max. 15 V continuous; 75 V for max. 1 ms
ANA
(sampling ratio 1:20)
Max. 50 mA DC
Yes
No