Air conditioner Installation manual AC***BXAP*G • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference.
Contents Contents Safety Information Installing the unit Power supply line, fuse or circuit breaker Installation Procedure Step 1 Choosing the installation location Step 2 Checking and preparing accessories and tools Step 3 Fixing the outdoor unit in place Step 4 Connecting the power cables, communication cable, and controllers Step 5 Optional: Extending the power cable Step 6 Connecting the refrigerant pipe Step 7 Optional: Cutting and flaring the pipes...
Page 3
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product and its electronic accessories should not be mixed with other commercial wastes for disposal. For information on Samsung’s environmental commitments and product-specific regulatory obligations, e.g. REACH, visit: www.samsung.com/uk/aboutsamsung/sustainability/environment/our-commitment/data/...
This manual explains how to install an indoor unit with • Do not use means to accelerate the defrost operation or a split system with two SAMSUNG units. The use of to clean, other than those recommended by Samsung. other types of units with different control systems may •...
• For use in Europe: This appliance can be used by • For this reason, when provisions of the installation children aged from 8 years and above and persons manual are not complied with, the cost required to with reduced physical, sensory or mental capabilities access and repair the units (in SAFETY CONDITIONS, or lack of experience and knowledge if they have been as set out in prevailing regulations) with harnesses,...
Safety Information • Make sure that the work area is safe from flammable • Never directly touch any accidental leaking refrigerant. substances. It could result in severe wounds caused by frostbite. • To purge air in the refrigerant, be sure to use a vacuum pump which is compatible with R-32.
Outdoor Unit 21.5 31.8 200 mm 23.0 34.0 Air Guide Duct (This product is not provided by Samsung) – m : Total refrigerant charge in the system • Install the unit at a height where its base can be firmly –...
Page 8
Check the installation site every 3 months and Sea breeze Sea breeze perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG (Code: MOK-220SA) or commercial water repellent grease and wax, etc., Outdoor Unit Outdoor Unit based on the product condition.
Page 9
Minimum clearances for the outdoor unit When installing 1 outdoor unit (Unit: mm) or more or more or more or more 300 or more 300 or more 1000 150 or 150 or or more more more CAUTION or more • The outdoor unit must be installed according to the specified distances in order to permit accessibility from each side, to guarantee correct operation, maintenance,...
Installation Procedure Moving the outdoor unit with wire rope Step 3 Fixing the outdoor unit in place Install the outdoor unit on a rigid and stable base to prevent Before carrying the outdoor unit, fasten two wire ropes of disturbance from any noise caused by vibration. When 8 m or longer, as shown in the figure.
Optional: Fixing the outdoor unit to a wall with NOTE a rack • Especially, if your outdoor unit is the one designed for Russian and European markets, consult the supply authority, if necessary, to estimate and reduce the supply system impedance before installation. Designed to cut off residual vibration from outdoor unit to rack.
Page 12
Installation Procedure Connecting the main power cable When using ELB for 1 phase and 3 phase 1-phase Electrical component box Power supply 1(L) 2(N) MCCB Cable tie Outdoor-to- Main power Communication cable indoor power cable cable 3-phase 1(L) 2(N) L1(R) L2(S) L3(T) The appearance of the unit may be...
Page 13
Main power terminal block specifications • 1-phase terminal block specifications • 3-phase terminal block specifications (Unit: mm) (Unit: mm) AC100/120/140RXADKG AC100/120/140RXADNG 1(L) 2(N) 1(L) 2(N) L1(R) L2(S) L3(T) 10.1 10.1 16.3 11.4 14.2 11.4 Main power cable specifications The power cable is not supplied with air conditioner. •...
Page 14
Installation Procedure 3- phase Model Outdoor unit Input current (A) Power supply Voltage range (V) Outdoor unit Indoor unit Outdoor unit Indoor unit Total MCA(A) MFA(A) Rated Min. Max. Cooling Heating AC071BN4PKG/EU 16.1 16.1 17.6 17.6 17.6 AC071BN6PKG/EU 16.1 16.1 17.6 17.6 17.6...
Page 15
Silence mode controller wiring diagram 3-phase 4Pin(RED) Indoor Unit 2Pin (RED) Outdoor Unit 1(L) 2(N) L1(R) L2(S) L3(T) Non-voltage contact External controller Cable tie Outdoor-to-indoor 3-phase 4-wire main Communication Connecting the outdoor-to-indoor power cable power cable (AC 380V) power cable cable and the communication cable NOTE...
Page 16
Installation Procedure Outdoor-to-indoor power terminal specifications • Connect the cables to the terminal board using the compressed ring terminal. • Cover a solderless ring terminal and a connector part of the power cable and then connect it. Silver solder Norminal Norminal dimensions dimensions...
Outdoor-to-indoor power and communication As shown in the figure, peel off the shields from the rubber and wire of the power cable. cables specifications • Peel off 20 mm of cable shields from the pre- installed tube. Indoor power supply (Unit: mm) Power supply Max/Min (V)
Page 18
Installation Procedure Using a crimping tool, compress the two points and flip After tube contraction work is completed, wrap it with the it over and compress another two points in the same insulation tape to finish. location. Three or more layers of insulation are required. •...
Step 6 Connecting the refrigerant pipe Maximum allowable length Items Single Installation DPM Installation AC100BXAPKG AC100BXAPKG AC071BXAPKG AC100BXAPNG AC071BXAPKG AC100BXAPNG Applicable outdoor unit models AC071BXAPNG AC120BXAPNG AC071BXAPNG AC120BXAPNG AC140BXAPNG AC140BXAPNG Total pipe length (L1+…+Ln+1+a+b) 55 m 85 m Main pipe (L1) 55 m 85 m 35 m...
Installation Procedure Step 7 Optional: Cutting and flaring the CAUTION pipes • Be sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05 mm. If you use C1220T-O (Soft) pipe for Ø19.05 mm, Make sure that you have the required tools available. (pipe the pipe may burst open, which can result in an injury.
Check that the flaring is correct, referring to the • Nitrogen blowing pressure range is 0.02 to 0.05 MPa. illustrations below for examples of incorrect flaring. • If you need a pipe longer than specified in piping codes and standards, you must add refrigerant to the pipe. Otherwise, the indoor unit may freeze.
Installation Procedure Step 9 Connecting up and removing air in Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port the circuit as shown at the figure. CAUTION CAUTION • When installing, make sure there is no leakage. When •...
Check for gas leakage. Check if the stop valve is closed completely. • At this time, especially check for gas leakage from Charge the refrigerant through the service port of the the 3-way valve’s stem nuts(A port), and from the liquid stop valve.
Page 24
Installation Procedure Please fill in the following with indelible ink on the CAUTION refrigerant charge label supplied with this product and on this manual. • The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop •...
Page 25
Calculating the quantity of refrigerant to add The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist. Single installation outdoor unit Interconnection pipe length (m) Model...
Installation Procedure Connecting communication line and wired remote Instruction for installation and operation controller • You should install the DPM according to the above • In case of 2 indoor units connection installation specification and eliminate the factors that give electrical load to the both indoor units when installing and operating.
Step 13 Insulating the refrigerant pipes Once you have checked that there are no leaks in the system, you can insulate the piping and hose. To avoid condensation problems, place an insulator around each refrigerant pipe. A(Gas) No gap B(liquid) NOTE •...
Installation Procedure Step 14 Checking the earthing Insulation Type (Heating/Cooling) If the power distribution circuit does not have a earthing or the earthing does not comply with specifications, an earthing Standard High humidity Pipe size electrode must be installed. The corresponding accessories Pipe Remarks (mm)
Step 15 Performing final check and trial Condition 1: The outdoor temperature is below 10°C. operation Condition 2: All the temperature conditions should meet the defrost conditions. Check the power supply between the outdoor unit and the auxiliary circuit breaker. Indication on the display and action to take when an inverter fault is detected •...
Page 30
Installation Procedure View mode: When the K4 switch is pressed, you can see information about our system state as below. • For a function that is not supported, "-" is shown for SEG2, SEG3 or SEG4. K4 short Display contents SEG1 SEG2 SEG3...
Page 31
Display contents SEG1 SEG2 SEG3 SEG4 Main micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit) After short push 1 Inverter micom version Year (Dec) Month (Hex) Date (Tens digit) Date (Units digit) After short push 2 E2P version Year (Dec) Month (Hex)
Installation Procedure Option Input CAUTION SEG1 SEG2 SEG3 SEG4 Function item unit Cooling / Heating • Edited option will not be saved if you do not end the option operation setting as explained in above instruction. Dedicated (default) mode for Main Cooling operation cooling/...
Using the stop valve NOTE • Do not apply excessive force to the stop valve and always use special instruments. Otherwise, the Opening the stop valve stopping box can be damaged and the back sheet can leaks. Open the cap and turn the stop valve anticlockwise by •...
Maintenance Procedures Maintenance Procedures Performing the gas leak tests for repair Decommissioning In case of repair of the refrigerant circuit, the following The following requirements must be fulfilled before and while procedure must be kept to consider flammability. taking the decommissioning procedure: •...
Appendix Troubleshooting The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. Error Code Meaning Remarks...
Page 36
Appendix Error Code Meaning Remarks 1. Check the range of temperature limited for heating Heating operation restricted at outdoor temperature over operation E440 Theat_high value (default:30°C) 2.Check the outdoor temperature sensor 1. Check the range of temperature limited for cooling Cooling operation restricted at outdoor temperature below operation E441...
Technical specifications Model Net weight Net dimension (W x D x H) AC071BXAPKG 75.0 kg 940 mm x 330 mm x 998 mm AC071BXAPNG 74.0 kg 940 mm x 330 mm x 998 mm AC100BXAPKG 100.0 kg 940 mm x 330 mm x 1420 mm AC100BXAPNG 100.0 kg 940 mm x 330 mm x 1420 mm...
Page 38
Samsung, PO Box 12987, Blackrock, Co. Dublin. IE or Euro QA Lab. Saxony Way, Yateley, Hampshire GU46 6GG, UK This appliance is filled with R-32.