6: Point Programming For Evs Amplifiers; 7: Point Programming For Evs-Vcm, And Evs-Rvm - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Programming
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices, then press ENTER.
Select name for the point
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrow key to select the type (See Table 8.6). Then press ENTER.
7.
Press ENTER to edit point name. See Appendix A. Or, Press right arrow key to skip point name edit.
8.
Repeat Steps 1 through 7 for all points.
8.5.6 Point Programming for EVS Amplifiers
To program module points:
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then press ENTER.
Select name for the point
5.
Enter the point number, then press ENTER. Points 5-8 on EVS-50W or EVS-125W will not be available unless the EVS-CE4 is
installed.
6.
Press the up or down arrow key to select the type (notification or unused), then press ENTER.
7.
Press ENTER to edit point name. See Appendix A. Or Press right arrow key to skip point name edit.
8.
Repeat Steps 1 through 7 for all points.
8.5.7 Point Programming for EVS-VCM, and EVS-RVM
To program module points:
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then press ENTER.
Select name for the point
5.
Enter the point number. Press ENTER.
6.
Press the up or down arrow key to select the type (switch or unused). Press ENTER.
7.
Press the up or down arrow key to select the desired Function (See Table 8.7). Press ENTER.
8.
Press ENTER to edit point name. See Appendix A or Press right arrow key to skip point name edit.
9.
Repeat Steps 1 through 8 for all points.
102
M01 P001 CONSTANT
MODULE_1 CKT_1
Enter Pt or <= to Exit>
Figure 8.5 Programming Points Screen for the 5496 Module
M04 P004 NOTIF
MODULE_1 CKT_8
Enter Pt or <= to Exit>
Figure 8.6 Programming Points Screen for the EVS Amplifiers
M04 P004 SWITCH
MODULE_1 CKT_8
Enter Pt or <= to Exit>
Figure 8.7 Programming Points Screen for the EVS-VCM and EVS-RVM Modules
Select aux power type
point number
SYS
Select NOTIF or UNUSED
point number
SYS
Select SWITCH or UNUSED
point number
G001
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Point

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents