UPS5000-E-(30 kVA–180 kVA) User Manual (Integrated UPS) Issue Date 2022-12-30 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
3.2.6.1 Connecting a Remote EPO Switch NO TICE ● Huawei does not provide the EPO button or cable. Prepare them by yourself. The recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and protect the cable with a protective tube.
Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.
Turn on the battery switch and charge batteries until each battery has a voltage greater than the EOD voltage and 11.3 V/cell. If any unmentioned faults occur, see the alarm list or contact Huawei technical support. Issue 02 (2022-12-30)
Page 181
UPS5000-E-(30 kVA–180 kVA) User Manual (Integrated UPS) B Alarm List Alarm List NO TE This table lists only common alarms. For more information, contact Huawei technical support. Alarm ID Alarm Alarm Causes Solution (Alarm ID- Name Severity Cause ID) 0001-1...