Huawei UPS5000-E300K-SM Quick Manual

Hide thumbs Also See for UPS5000-E300K-SM:

Advertisement

Quick Links

UPS5000-E-(250 kVA-300 kVA)
Quick Guide (50 kVA Power Modules)
Issue: 09
Part Number: 31507656
Date: 2020-03-23
1
Overview
UPS Model
Cabling Mode
UPS5000-E-
Routed in and out from
300K-SM
the bottom
UPS5000-E-
Routed in and out from
300K-SMT
the top
UPS5000-E-300K-SM
(1) Power modules
(3) Control module (CM)
(5) Monitor display unit (MDU)
(7) Maintenance bypass switch
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
Capacity
Weight
440 kg
250 kVA,
300 kVA
450 kg
UPS5000-E-300K-SMT
(2) Bypass module
(4) Power distribution subrack cover
(6) Filler panels
(8) Folder
1
Dimensions (H
x W x D)
2000 mm x 600
mm x 850 mm

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E300K-SM

  • Page 1 UPS5000-E-(250 kVA-300 kVA) Quick Guide (50 kVA Power Modules) Issue: 09 Part Number: 31507656 Date: 2020-03-23 Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. Overview Dimensions (H UPS Model Cabling Mode Capacity Weight x W x D) UPS5000-E-...
  • Page 2: Installing The Ups

    2. Use insulated tools during installation and operation. 3. Only Huawei engineers or engineers certified by Huawei are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
  • Page 3: Connecting Cables

    Non-Secured Installation 1. Lower the four leveling feet at the bottom of the cabinet by using a wrench until all the four castors at the bottom hang in the air and the leveling feet bear the whole cabinet weight. 2. Check whether the bottom of the cabinet is horizontal by using a level.
  • Page 4 1. This document describes cable routing by removing the top cover when there are two mains inputs. 2. In the case of single mains, you do not need to connect bypass input power cables and remove short-circuit copper bars. Connecting Cables to the UPS5000-E-300K-SM 1.
  • Page 5 5. Connect the mains and bypass input power 6. Connect the output power cable. cables. 7. Connect the battery cable. The wire routed from the middle point of positive and negative battery strings is the neutral wire. The following figure shows a neutral wire routed from the middle of two battery strings consisting of 40 batteries, half positive and half negative.
  • Page 6 Connecting Cables to the UPS5000-E-300K-SMT 1. The basic rule is to route cables from inside out and from the bottom up. 2. If holes are drilled for routing cables, attach grommet strips on the hole edges to protect cables. 1. Remove the cover from the power 2.
  • Page 7 4. Connect ground cables to the UPS. 5. Connect mains and bypass input power cables. • : Internal equipotential connection • : Protection ground 6. Connect output power cables. 7. Connect battery cables.
  • Page 8: Verifying The Installation

    8. Route the signal cable. Bind cables to the cabinet. The figure shows signal cables Route a neutral wire from the middle of routed from the top of the cabinet. the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example.
  • Page 9: Powering On And Starting The Ups

    138–485 V AC, and the frequency range is 40–70 Hz. Powering On the UPS Close the upstream bypass and mains input switches. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 10 Initial Startup • If the UPS is powered on for the first time, you need to obtain the startup password from the Service Expert app. Skip this step if the UPS is not powered on for the first time. • The Service Expert app can be downloaded from Google Play Store and can run on Android.
  • Page 11 2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen. 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault. 4.
  • Page 12: Shutting Down The Ups

    Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each battery string and then turn on the general circuit breaker between battery strings and the UPS.
  • Page 13 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: https://support.huawei.com/enterprise https://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...

Table of Contents