Huawei UPS5000-S Series Quick Manual

Huawei UPS5000-S Series Quick Manual

Hide thumbs Also See for UPS5000-S Series:

Advertisement

Quick Links

UPS5000-S-(50 kVA-300 kVA)
Quick Guide (Isolation Protection)
Issue: 05
Part Number: 31500BBT
Date: 2020-11-24
1
Overview
UPS Model
UPS5000-S-200K-FM
UPS5000-S-300K-SMT
UPS5000-S-200K-FM
(1) Cover
(3) Bypass input switch (4) Maintenance bypass switch
(5) Output switch
(7) Bypass module
(9) Monitor display
unit
Cabling Mode
Capacity
50 kVA, 100
Routed in and
kVA, 150 kVA,
out from the
200 kVA, 250
top
kVA, 300 kVA
(2) Mains input switch
(6) Control module
(8) Power modules
(10) Folder
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
Weight
380 kg
460 kg
UPS5000-S-300K-SMT
(1) Cover
(3) Control
module
(5) Power
modules
1
Dimensions (H x W x D)
2000 mm x 600 mm x
850 mm
(2) Maintenance
bypass switch
(4) Bypass module
(6) Monitor display
unit

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-S Series

  • Page 1 UPS5000-S-(50 kVA-300 kVA) Quick Guide (Isolation Protection) Issue: 05 Part Number: 31500BBT Date: 2020-11-24 Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. Overview UPS Model Cabling Mode Capacity Weight Dimensions (H x W x D) 50 kVA, 100...
  • Page 2: Installing The Ups

    2. Use insulated tools during installation and operation. 3. Only Huawei engineers or engineers certified by Huawei are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
  • Page 3: Connecting Cables

    Non-Secured Installation 1. Lower the four leveling feet at the bottom of the cabinet by using a wrench until all the four castors at the bottom hang in the air and the leveling feet bear the whole cabinet weight. 2. Check whether the bottom of the cabinet is horizontal by using a level.
  • Page 4 Connecting Cables to the UPS5000-S-200K-FM 2. (Skip this step if the mains input and bypass 1. Ensure the maintenance bypass switch is OFF. input share a power source.) Remove the Open the front door, remove the front cover, copper bars between the mains input and and remove covers from the top of the bypass input.
  • Page 5 4. Connect battery cables and output cables. Connecting Cables to the UPS5000-S-300K-SMT 1. Ensure the maintenance bypass switch is OFF. 2. (Skip this step if the mains input and bypass Open the front door, remove the front cover, input share a power source.) Remove the and remove covers from the top of the copper bars between the mains input and cabinet based on the site requirements.
  • Page 6 3. Connect the ground cable, power cables, and signal cable. There is no need to connect the bypass input power cable if the mains input and bypass input share a power source. signal cable Port Bolt Torque Description Specifications M12 x 45 46N•m Mains input M12 x 45...
  • Page 7: Verifying The Installation

    Verifying the Installation 1. Check that there is no foreign matter in the cabinet. UPS5000-S-200K-FM UPS5000-S-300K-SMT (1) Rear of modules (2) Cabinet top (3) Wiring terminal blocks (4) Switches 4. Do not remove the dustproof cover 2. After verifying the installation, reinstall all the before power-on to prevent dust inside covers.
  • Page 8 Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. Initial Startup If the UPS is powered on for the first time, you need to obtain the startup password from the •...
  • Page 9 2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen. 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
  • Page 10: Shutting Down The Ups

    System User LCD Preset Password WebUI Preset Password admin (system 000001 Changeme administrator) operator (common user) 000001 Changeme Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears from the MDU. 2.
  • Page 11 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: https://support.huawei.com/enterprise https://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...

This manual is also suitable for:

Ups5000-s-200k-fmUps5000-s-300k-smt

Table of Contents