E6581422③ TOSVERT VF-S11 Option Instruction Manual CCL002Z NOTICE 1. Make sure that this instruction manual is delivered to the end user of the CC-Link option for the VF-S11. 2. Read this manual before installing or operating the CC-Link option unit, and store it in a safe place for reference.
Page 2
E6581422③ Safety precautions On the inverter and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to the inverter along with this instruction manual for completely understand the safety precautions, the symbols and indications shown below.
Page 3
E6581422③ Limitation of use Safety precaution ▼ Never use this unit with any device other than TOSVERT VF-S11 series inverters. Doing so may cause an accident. Handling in general Warning Never disassemble, modify or repair the product. ▼ Disassembling the product may cause electric shocks, fire or injuries. Disassembly prohibited For repairs, call your sales/repair agency.
Page 4
E6581422③ Wiring Warning ▼ Turn off input power before installing and wiring this option. Wait at least 10 minutes and check to make sure that the charge lamp (VF-S11) is no longer lit. Mandatory ▼ Tighten the screws on the terminal block to the specified torque (Refer to Section 3.2 and 3.3).
Page 5
E6581422③ Preface Thank you for purchasing a “CC-Link Option (CCL002Z)” for TOSVERT VF-S11 inverter. This option can connect with open field network CC-Link and data communications with the CC-Link master through installing this option in the VF-S11 and using it. Besides this instruction manual, the "CC-Link option Function Manual"...
E6581422③ - Table of contents - 1. Overview···················································································································································6 2. Name of functions of main parts ··············································································································6 2.1. Exterior features······························································································································6 2.2. RJ45 Connector for options (CN2) ·································································································7 2.3. Termination resistor selection switch (SW4)···················································································7 3. Installing the CCL002Z·····························································································································8 3.1. Description of terminals ················································································································10 3.2.
E6581422③ 1. Overview This option allows the VF-S11 inverter to be connected into a CC-Link network. CC-Link supports a maximum of 42 nodes, allowing for the Master unit and this option is based on CC-Link Ver.1.10. The CCL002Z is able to operate RUN/STOP, monitor the status of the inverter, set the inverter's parameter and etc.
E6581422③ Behavior of LED State of LED Cause L.RUN L.ERR Normal communication is made but CRC error has occurred due to noise. Normal communication Hardware fault Hardware fault Cannot answer due to CRC error of receive data. Data sent to the host station does not reach destination. Hardware fault Hardware fault (It is an unstable state by disconnection, etc.) Polling response is made but refresh receive is error in CRC.
E6581422③ 3. Installing the CCL002Z Install the CC-Link communication option to VF-S11 as follows. (1) Turn off the input power of VF-S11 and wait for at least 10 minutes and then check that the CHARGE lamp on VF-S11 is no longer lit. (2) Open the VF-S11 front cover, remove the terminal board fixing screw and take off the VF-S11 standard terminal board.
Page 10
E6581422③ VF-S11 unit (Over 5.5kW) Terminal board fixing screw (M3 screw tightening torque: 0.7 to 0.8Nm) Cabling label position Board fixing screw hole Board catching pin Example Type form label(attached) Stick the CCL002Z type form label like bellow figure. CCL002Z VF-S11 nameplate CC-Link terminal label(attached) Stick the label to the CC-Link terminal.
E6581422③ 3.1. Description of terminals <Control terminals specification> Terminal Input/ Electrical Function Symbol Output specifications This terminal is Multifunction programmable contact input. Shorting across F-CC causes forward rotation; open causes deceleration stop. (Across ST-CC is short state.) Voltage free contact Input input.
E6581422③ 3.2. Connection of control terminals Observe the following when wiring. ▼ Keep the control signal cables 20cm or more separate from the power cables to prevent from malfunctioning due to electromagnetic noise. ▼ Use 0.14 to 1.5mm solid/stranded wire (AWG 28 to 16) for control cables. *Provide an inter-lock system stated in below, when using a programmable controller that has the open collector output.
E6581422③ Fix the communication cables after wiring. If take care of the wire end, use below parts. Manufacture : Phoenix contact corp. Part Number : AI 0,5-8 WH (connect one wire) Part Number : AI-TWIN2x0,5-8 WH (connect two wires) Length : 8mm 3.4.
E6581422③ 4.2. Basic functions This clause shows the basic function of this CC-Link option using by CC-Link communication. 4.2.1. Run and frequency operation command The PLC program can operate the inverter to run, stop, set the operation frequency and change the parameters. If the PLC controls these operations, select the command mode and the frequency setting mode.
E6581422③ 4.2.4. Disconnection error of network cable Disconnection of a CC-Link network cable, operation at the time of the abnormalities in communication, detection, etc. are set up with the following parameter of the VF-S11. f892: [Inverter operation at disconnection] Default: 0 0: Inverter stop, communication command, frequency mode open 1: None (continued operation) 2: Deceleration stop...
E6581422③ 5. List of CC-Link data This option occupies one station area of the buffer memory of the PLC. 5.1. RX(Monitor), RY(Instruction) List of remote I/O Inverter (Slave) PLC (Master) PLC (Master) Inverter (Slave) -> -> Device No. Signal Device No. Signal RXn0 Forward running...
E6581422③ 6. CC-Link local/Remote Operation The example below shows how to configure the VF-S11 for local/remote operation. F terminal....Operating command R terminal ....CC-Link local/remote (Terminal in this example) switching VIA terminal....Operation frequency command <Wiring> VF-S11 Variable resistor for adjustment: 1/4W-4.7k ohm 10k ohm Frequency setting (Variable resistor: 1 to 10k ohm)
4) Damage due to the use of CC-Link communication option for non-intended purposes. 4. Unless a service contract is signed beforehand between the customer and Toshiba, in witch case the service contract has priority over this warranty.