If take care of the wire end, use below parts.
*
3.4. Wiring / Connection with the CC-Link master
The example of wiring/connection with the CC-Link master unit is shown in the following
figure.
DA
CC-Link
DB
DG
Master Unit
SLD
*1
FG
*1: As for master station, when use the Mitsubishi Electric An series, the recommended version is "LS" or later.
•
Connection of Several Inverters
Factory Automation can be applied with several inverters which share CC-Link system as
a remote device station, and are controlled and monitored by PLC user programs.
Manufacture : Phoenix contact corp.
Part Number : AI 0,5-8 WH
Part Number : AI-TWIN2x0,5-8 WH
Length
: 8mm
DA
DB
DG
SLD
FG
The example of wiring with the inverter VF-S11
* Communication terminal DA, DB
Set up the network using shielded twisted pair cable.
* Communication terminal DG
* Shield connection terminal SLD
Please connect the shield line of the dedicated CC-Link cable with the SLD
terminal.
* Connection of the frame ground terminal FG
Grounding resistance is 100 ohm max.
* Termination resistor
Switch of the SW4 and choose a 110ohm-termination resistor.
Note: Please use 130 ohm, 1/2W resistors when use the high performance CC-Link
(
dedicated cable.)
Fix the communication cables after wiring.
*
7mm
(connect one wire)
(connect two wires)
R/L1
S/L2
T/L3
CCL002Z
- 12 -
U/T1
Inverter
V/T2
VF-S11
W/T3
E6581422③
Motor
IM