HP StorageWorks
Replacing an HSG60 or
HSG80 Array Controller
Read instructions completely before
beginning the installation procedure
Copyright 2000–2005 Hewlett-Packard Development Company, L.P.
©
Hewlett-Packard Company makes no warranty of any kind with regard to
this material, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose. Hewlett-Packard shall
not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this
material.
This document contains proprietary information, which is protected by
copyright. No part of this document may be photocopied, reproduced,
or translated into another language without the prior written consent of
Hewlett-Packard. The information contained in this document is subject to
change without notice.
Microsoft®, MS Windows®, Windows®, and Windows NT® are U.S.
registered trademarks of Microsoft Corporation.
Product names mentioned herein may be trademarks of their respective
companies as reflected by an associated footnote.
Hewlett-Packard Company shall not be liable for technical or editorial
errors or omissions contained herein. The information is provided "as is"
without warranty of any kind and is subject to change without notice. The
warranties for Hewlett-Packard Company products are set forth in the
express limited warranty statements for such products. Nothing herein
should be construed as constituting an additional warranty.
Replacing an HSG60 or HSG80 Array Controller Installation
Instructions
Sixth Edition (March 2005)
Part Number: EK-80CTL-IM. F01
Installation
Instructions
About these instructions
This document contains instructions for replacing an
HP StorageWorks HSG60 or HSG80 array controller. Array
controller replacement procedures in these instructions
include:
Replacing HSG60 and HSG80 controllers in
single-controller
configurations, page 3
Replacing HSG60 and HSG80 controllers in
dual-redundant controller
Prerequisites and special considerations
Observe the following prerequisites and special considerations
before replacing an HSG60 or HSG80 array controller:
Single-to-Dual-redundant configuration upgrades—For
instructions on upgrading a single-controller configuration
to a dual-redundant controller configuration, refer to the
appropriate documentation that shipped with your array
controller or subsystem component.
DRM Configurations—If you are using HP StorageWorks
Data Replication Manager (DRM) with HSG60 or HSG80
controllers that need to be replaced, refer to the HP
StorageWorks HSG60 and HSG80 Array Controller and
Array Controller Software Maintenance and Service Guide
for specific instructions. A copy of this guide can be
downloaded from the HP website at:
http://h18006.www1.hp.com/products/storageworks/
acs/index.html
.
Hardware Compatibility—The replacement controller
hardware must be compatible with the remaining controller
hardware. Refer to product-specific release notes and
documentation for information regarding hardware
compatibility.
Software Compatibility—The software versions and
patch levels of the replacement controller must be the same
as that of existing subsystem controllers.
General information
Figure
1,
Figure
2, and
Figure 3
information about the HSG60 and HSG80 array controllers and
specific host cable connections for each array controller type.
Tip:
See the applicable array controller figure
or
Figure 3
on page 2) for clarification during the selected
procedures.
Note:
The maintenance port cable shipped with the array controller
has a 9-pin connector for a PC connection only. If you are using a
terminal instead of a PC, obtain the optional maintenance port
cable.
configurations, page 5
(on page
2)
provide general
(Figure
1,
Figure
2,

Advertisement

loading

Summary of Contents for HP StorageWorks HSG60

  • Page 1 Read instructions completely before Data Replication Manager (DRM) with HSG60 or HSG80 beginning the installation procedure controllers that need to be replaced, refer to the HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software Maintenance and Service Guide for specific instructions.
  • Page 2 5033 5034 1 Backplane connector 8 Fibre Channel optical host 1 Backplane connector 8 Fibre Channel copper host bus adapter 2 Access door bus cables 2 Access door 9 Maintenance port cable for a 3 Optical gigabit link module 9 Maintenance port cable for a 3 Copper GLM PC connection (GLM)
  • Page 3: Removing A Controller

    Replacing HSG60 and HSG80 controllers Note: After the controller shuts down, the Reset button and the first in single-controller configurations three LEDs turn on (see Figure 5). This can take several minutes to occur, depending on the amount of data that needs to be flushed from the cache module.
  • Page 4: Installing A Controller

    If the cache is not good, refer to Table 14 through Table 16 in the “Controller and Cache Replacement Troubleshooting” appendix of the HP StorageWorks HSG60 and HSG80 Array Controller and Array Controller Software Maintenance and Service Guide.
  • Page 5 Removing a controller 13. Determine whether the configuration restore process completed successfully, and then perform one of the following options: Perform the following steps to remove a controller in a dual-redundant controller configuration: Perform the following substeps if the configuration restore process did not complete If the controller to be replaced ( ) is functional, successfully.
  • Page 6 c. Enter option 1 to remove the controller or cache Note: In Transparent Failover mode, units that failed over due to a module. The Replace or remove Options RESTART command will revert back to preferred controller after screen is displayed (see Figure 11).
  • Page 7 (Refer to instructions for installing a Installing a controller cache module in a dual-redundant controller configuration of the HP StorageWorks HSG60 Perform the following steps to install a controller in a and HSG80 Array Controller and Array dual-redundant controller configuration if only the controller is...
  • Page 8 3b, refer to Table 14 through Table 16 in the “Controller and Cache Replacement Troubleshooting” appendix of c. Press and hold the Reset button, insert the the HP StorageWorks HSG60 and HSG80 program card, and continue holding the Reset Array Controller and Array Controller button.
  • Page 9 The replacement controller can fail with a recursive bugcheck (halting with OCP code 25), and the Reset button LED remains steady on. Contact HP technical support or replace the controller if this condition occurs. Disconnect the PC or terminal from the controller maintenance port of the operational controller.