10.2
Technical data
Circuit-breakers for fixed installation

10.2.1 Performance data and weights

Rated voltage
Rated frequency
Rated lightning impulse withstand voltage
Rated power frequency withstand voltage
Rated of rise of transient recovery voltage
Peak transient recovery voltage
Rated operating sequence
Rated operating sequence for autoreclosing
Guideline values for function times:
Closing time
Opening time
Arcing time (at 50 Hz)
Break time
Minimum command time on closing
Minimum command time on opening
Breaker
Rated
Rated
type
voltage
current
VM1..
kV
A
1231-25
12
3150
1240-25
4000
3)
3)
1231-31
3150
1240-31
4000
3)
3)
1212-40
1250
1216-40
1600
1220-40
2000
1225-40
2500
1231-40
3150
1240-40
3)
4000
3)
1212-50
1250
1216-50
1600
1220-50
2000
1225-50
2500
1231-50
3150
1240-50
4000
3)
3)
At operating voltages lower than the rated voltage, the same values fundamentally apply as for the rated voltage. Higher values on request.
1)
Individual unit without truck
2)
3)
Breakers for 4000 A with fan cooling
kV
12
Hz
50/60
kV
75
kV
28
kV/µs
0.34
kV
20,6
ca. 45...60 ms
ca. 35...50 ms
≤ 15 ms
≤ 60 ms
20 ms
20 ms
Rated
Short-
Rated
short-
circuit
short-
circuit-
breaking
circuit
breaking
currentr
making
current
asymm.
current
1)
symm.
(peak)
1)
kA
kA
kA
25
27.3
31.5
34.3
80
40
43.6
100
50
54.5
125
O-3 min-CO-3 min-CO
O-0,3 s-CO-3 min-CO
Rated
Pole
short-
centres
circuit
duration
1)
s
63
3
275
275
3
275
275
3
210
210/275
210/275
210/275
275
275
3
210/275
210/275
210/275
210/275
275
275
Instruction manual 504/05 | VM1 Vacuum circuit-breaker 35
17.5
50/60
95
38
0.42
30
Weight
Permissible
2)
number
of vacuum
interrupter
switching
operations
mm
approx.
Figure
kg
10a/10b
Page 33/34
235
Diagram C
235
Diagram C
235
Diagram D
235
Diagram D
135
Diagram E
135/142
Diagram E
135/142
Diagram E
141/148
Diagram E
235
Diagram E
235
Diagram E
232/240
Diagram F
232/240
Diagram F
232/240
Diagram F
232/240
Diagram F
245
Diagram F
245
Diagram F
Dimen-
sional
drawings
Figure-no.
10/2
10/2
10/2
10/2
10/1
10/1
10/2
10/2
10/2
10/2
10/3
10/3
10/3
10/3
10/3
10/3

Advertisement